ATTENTION!
If you do not press any keys after entering the password or do not change the settings via MODBUS, password protection
is re-enabled after the password activation time has elapsed.

3.4.6 RS485 Settings Menu (485)

Use this menu item to set the baudrate, slave ID and parity control settings in RS485 communication. Please see
Table 3-3 for the menu tree and Section 5 for the factory default settings.

3.4.7 Clear Menu (CLr)

Use this menu to delete the stored values in the memory and restore the factory settings. Please see Table 3-3
for the menu tree and Section 5 for the factory default settings.
The following options are available in the clear menu:
„ OFF: Disables the clear process.
„ All: Clears all values stored in the memory and restores them to the default factory settings.
„ Enr: Resets all energy counters.
„ Cnt: Resets all counters.
„ HI: Clears the maximum values stored in the memory.
„ LO: Clears the minimum values stored in the memory.
„ dEd: Clears the demand values stored in the memory.
„ Set: Restores all settings to the factory settings.
„ ALr: Restores the alarm settings to the factory settings.
In order to prevent an accidental deletion, "nO"/"YES" prompt is displayed if you choose any option other than "OFF".
„ To confirm the action:
Press the right key to blink the "nO" sign. Use the up/down keys to change the "nO" to "YES". Then, press
the left key to confirm the action.
„ To discard the action:
Press the right key to blink the "nO" sign. Then, press the left key to confirm the "nO" option and exit the
menu without making any deletions.
ATTENTION!
The device restarts if you choose SEt, ALr or All and confirm the action. It will not restart if you choose other options. It will
clear the values and returns back to the CLr menu.

3.5 SAVE PROCEDURE

3.5.1 Changing Value/Setting

There are 2 different menus for changing the values:
„ l Multiple choice menus: These menus contain predefined options. Press the right key to choose and blink
the first variable of the menu. Press the up/down keys to choose and blink the desired option. Then press
the left button to complete your choice.
„ l Menus with numerical input values: In these menus, move through the digits to set the desired value. Press
the right key to choose and blink the first digit of the variable from the left. Use the right key to move through
the digits. Use the up/down keys to increase/decrease the value of the active digit. Set the desired values for
variables by setting the individual digit values and press the left key to complete your action.