Page 2
MMW03-CH - Multimeter Designed to measure: Phase-Neutral Voltage; Phase-Phase Voltage; ➢ Phase Current; Neutral Current; ➢ Frequency; ➢ ⱷ ; Power factor; ➢ Active power; Reactive power; Apparent power; ➢ THDv, THDi, ➢ Voltage and current harmonics up to the 31 order (over ➢...
Page 3
MMW03-CH - Multimeter Other functions: Indication of phase loss and phase sequence error ➢ It determines and saves, in the memory, the maximum and ➢ minimum values of: Voltage; ✓ Current; ✓ Frequency; ✓ cosφ and power factor; ✓ THDv; THDi;...
Page 4
MMW03-CH - Multimeter Other functions: Current, voltage, frequency, cosφ and power factor alarms ➢ Stores: ➢ Hour meter; ✓ Total time energized; ✓ Total time de-energized; ✓ RS485 communication with MODBUS RTU protocol; ➢ 2 alarm output relays; ➢ 4-digit password;...
Front panel Output relays and alarm; Phases Kilo and Mega Instant measurement indicators Capacitive indication per phase and of the system Indicators (7 segments) Arrow keys Maximum or minimum value indicator...
Page 7
Indicators L1, L2 and L3 L1, L2, L3 flashing simultaneously and very slowly (1 per second): • Error in the phase sequence - voltage; None/all of L1, L2, L3 flashing slowly (1 for 0.5 second): • Voltage loss in one or all connections None/all of L1, L2, L3 flashing slowly (1 for 0.2 second): •...
Page 9
Measurement menus V F-N Phase-Neutral Reading (F-N) Phase 1 - F-N Voltage Phase 2 - F-N Voltage Phase 3 - F-N Voltage F-N average voltage Line frequency...
Page 19
Measurement menus – V (L-N) Maximum and minimum menus The maximum and minimum values are calculated and stored in non-volatile memory for the following parameters ➢ Voltage (F-N and F-F) ➢ Neutral current ➢ Frequency ➢ Cosφ ➢ Power factor ➢...
Page 20
Measurement menus Demand Menus The demand values are calculated and stored in non- volatile memory for the following parameters: ➢ Current ➢ Active power ➢ Reactive power ➢ Apparent power To view max. and min. and demand menus, use the left and right arrow keys.
Page 21
Measurement menus If the system consumes energy, (P) must be positive. If the active power display (P1, P2 or P3) is flashing in L-H or instant menu, reverse the input connection of the current transformer (k-l)
Page 22
Energy measurement menus To access the ENERGY menu, use the UP and DOWN arrow keys Available energy parameters: • Import active energy (I.Ac) • Export active energy (E.Ac) • Import reactive energy (I.rE) • Export reactive energy (E.rE)
Page 23
Energy measurement menus Preset value: In any menu on the device, press for at least 2 seconds and release. The menu will start flashing. Using the right arrow key, move the indicator to the digit you want to change. Enter the desired value using the up and down arrow keys.
Meters menu To navigate to the Meters menu, use the Up and Down arrow keys "On hour" Meter: The display shows the total hours that the equipment was energized. "Run hour" Meter: It shows the time the device performed the measurement. It is necessary that the signal inputs be fed by the three current phases and three voltage phases.
Settings menu The settings are done in the SEt menu. To navigate to the settings menu, use the Up and Down arrow keys...
Page 27
Settings menu - basic In this menu, it is defined: • Current transformer ratio - CTR • Voltage transformer ratio - VTR • Connection type - 3P4W (star) or 3P3W (delta) Connectio CTR: 1-5000 BASIC VTR: 1.0-5000.0 CONNECTION: STAR (3P4W), DELTA (3P3W)
Page 28
Settings menu - Alarm In this menu, the alarm limits, hysteresis and alarm holding time are configured. ALARMS: - U (L-N), ULL (L-L), - I (current), In (I neutral), - COSφ, PF,...
Page 29
Settings menu - Alarm U (Voltage L-N) Holding time Lower Hysteresis Upper limit limit When the alarm limit is exceeded: • "k" and "M" LEDs of the respective parameter start flashing at the same time. • After the holding time has elapsed, the "ALM" LED turns on; if the alarm relay is programmed to operate, OUT1 and/or OUT2 LEDs turn on and the respective relay is energized.
Page 30
Settings menu - Alarm In this menu, the operating conditions of the alarm relays are defined Relay 1/2: OFF, LO, HI The alarm relays can be programmed to: • OFF : Relay is not energized in an alarm condition • LO : Relay is activated when the lower limit alarm is triggered •...
Page 31
Settings menu - Demand In this menu, the demand time conditions are defined. After defining the period, which may be from 1 to 60 minutes, the demand values are calculated periodically considering this time.
Page 32
Settings menu - Password In this menu, it is defined: - Activate the password or not; - Define password; - Password activation time; Activation Pin Time Change Act - Activation: Enable/Disable password protection (NO/YES) P t - Pin Time: Time to request password again. When any key is pressed after entering the password or no change is made via MODBUS, the password protection is activated after the preset time has elapsed (1-60min)
Page 33
Settings menu - RS485 In this menu, the MODBUS RTU, RS485 communication parameters are defined: - Baud Rate - Network communication rate; - Slave ID; - Parity control Baud Rate Parity Baud Rate: Options of (1200/2400/4800/9600/19200/38400/57600) Slave ID of (1-247) Parity: Parity check definition (None, Even, Odd)
Page 34
Settings menu - Clear In this menu, the values stored in the machine's memory are deleted and the factory values are restored. • OFF : Disable the "clear" process • All : Clear all stored values and restores factory settings •...
Page 35
Settings menu - Version This menu shows the device firmware version...
Page 36
SAVE procedure Press the left arrow key up to the "SAU" screen. Press the key until "YES" or "NO" is shown to confirm the changes in the settings or not. To confirm the changes: Press the right button until "YES" flashes. Then press the left arrow key to save the changes.
Need help?
Do you have a question about the MMW03-CH and is the answer not in the manual?
Questions and answers
o multimedidor Liga mais so aprece zeros