• If it is necessary to increase the height of the drain
pipe, install the drain pipe straight within 300 mm
from the drain hose port. If it is raised higher than 550
mm, there may be water leaks.
Drain hose
Band joint
• Do not give the hose an upward gradient beyond the
connection port. This will cause water to flow backwards
when the unit is stopped, resulting in water leaks.
• Do not apply force to the piping on the unit side when
connecting the drain hose. The hose should not be
allowed to hang loose from its connection to the unit.
Fasten the hose to a wall, frame or other support as
close to the unit as possible.
Hanger
Main drainpipe
CAC R-32_Mini 4way_IM_DB68-08129A-00_EN_20181211.indd 13
20 mm or more
1/100 or more
550 mm or
300 mm or
less
less
Ceiling
Under gradient
Ceiling
Support pieces
1 to 1.5 m
1/100 or more
Ceiling
Individual
air vent
• Install horizontally.
Be horizontal
Indoor unit
Flexible hose
• Max. allowable axis gap.
Indoor unit
• Max. allowable bending angle.
Indoor unit
NOTE
• If a concentrated drain pipe is installed, refer to the
figure below.
1~1.5m
Centralized horizontal drainpipe
(more than 1/100 slope)
Max. 20 mm
Max. 30˚
Main air vent
550mm or less
13