Mounting And Installation; Creating A Zoning Plan - Honeywell HCE80R Mounting And Operation Manual

Table of Contents

Advertisement

Available languages

Available languages

6

Mounting and installation

Creating a zoning plan

Within a building rooms (zones) can be controlled with different room
setpoint temperatures. The thermal actuators of the allocated zone (room)
are controlled depending on the room setpoint temperature.
!
A maximum of 5 temperature zones can be
set up for each underfloor heating controller.
This number can be increased to 8 by
using the expansion module HCS80.
A maximum of 3 thermal actuators
can be connected in each zone.
Specifying temperature zones
Specify the number of zones and
1
the corresponding rooms.
Allocate the corresponding room device,
2
for example HCW82 and the required
thermal actuators to each zone.
Label the room devices and thermal actuators for the
3
respective zone (see fold-out page Fig. 4, Z1...Z8).
Explanation of the example
• The living area is covered by six temperature
zones. The additional module HCS80
is required for this partitioning.
• The underfloor heating controller
controls 8 thermal actuators.
Mounting and installation
Temperature
zones (maximum)
16
24
Thermal actuators
(maximum)
8
24
48
72
Number of
underfloor heating
controllers
1
2
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

Hcc80rHce80Hcc80

Table of Contents