Beckhoff SCT Series Documentation page 66

Current transformers (ct) for energy measurement
Hide thumbs Also See for SCT Series:
Table of Contents

Advertisement

Technical data, functional description, installation
SCT7325 | Busbar split-core current transformer for primary currents 750...1500 A, accuracy class 0.5
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 68] (W x H x D)
Versions
SCT7325-0750
SCT7325-1000
SCT7325-1500
SCT7415 | Busbar split-core current transformer for primary currents 1500...5000 A, accuracy class 1
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 68] (W x H x D)
Versions
SCT7415-1500
SCT7415-2000
SCT7415-2500
SCT7415-3000
SCT7415-4000
SCT7415-5000
66
current ratio 750/5 A,
rated power 2.5 VA
current ratio 1000/5 A,
rated power 5 VA
current ratio 1500/5 A,
rated power 7.5 VA
current ratio 1500/5 A,
rated power 15 VA
current ratio 2000/5 A,
rated power 15 VA
current ratio 2500/5 A,
rated power 15 VA
current ratio 3000/5 A,
rated power 30 VA
current ratio 4000/5 A,
rated power 30 VA
current ratio 5000/5 A,
rated power 30 VA
Version: 1.1
SCT7325-xxxx
0.5
750...1500 A
5 A
80 mm
80 x 120 mm
3
155 mm x 198 mm x 58 mm
SCT7415-xxxx
1
1500...5000 A
5 A
80 mm
80 x 160 mm
4
195 mm x 243 mm x 79 mm