SCT2615 | Ring-type current transformers for primary current 2500 A, accuracy class 1
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 34] (W x H x D)
Approvals/markings
Versions
SCT2615-2500
SCT2625 | Ring-type current transformers for primary current 2500 A, accuracy class 0.5
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 34] (W x H x D)
Approvals/markings
Versions
SCT2625-2500
SCTxxxx
current ratio 2500/5 A,
rated power 15 VA
current ratio 2500/5 A,
rated power 15 VA
Version: 1.1
Technical data, functional description, installation
SCT2615-xxxx
1
2500 A
5 A
70 mm
80 x 30 mm, 100 x 10 mm
6
130 mm x 147 mm x 52 mm
CE
SCT2625-xxxx
0.5
2500 A
5 A
70 mm
80 x 30 mm, 100 x 10 mm
6
130 mm x 147 mm x 52 mm
CE