Sct7Xxx; Technical Data - Beckhoff SCT Series Documentation

Current transformers (ct) for energy measurement
Hide thumbs Also See for SCT Series:
Table of Contents

Advertisement

Technical data, functional description, installation
3.6

SCT7xxx

3.6.1

Technical data

SCT7105 | Busbar split-core current transformer for primary currents 100/200 A, accuracy class 3
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 68] (W x H x D)
Versions
SCT7105-0100
SCT7105-0200
SCT7115 | Busbar split-core current transformer for primary currents 250/400 A, accuracy class 1
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 68] (W x H x D)
Versions
SCT7115-0250
SCT7115-0400
SCT7125 | Busbar split-core current transformer for primary current 400 A, accuracy class 0.5
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 68] (W x H x D)
Versions
SCT7125-0400
64
current ratio 100/5 A,
rated power 1.25 VA
current ratio 200/5 A,
rated power 2.5 VA
current ratio 250/5 A,
rated power 1.5 VA
current ratio 400/5 A,
rated power 5 VA
current ratio 400/5 A,
rated power 1.0 VA
Version: 1.1
SCT7105-xxxx
3
100/200 A
5 A
20 mm
20 x 30 mm
1
93 mm x 106 mm x 58 mm
SCT7115-xxxx
1
200/400 A
5 A
20 mm
20 x 30 mm
1
93 mm x 106 mm x 58 mm
SCT7125-xxxx
0.5
400 A
5 A
20 mm
20 x 30 mm
1
93 mm x 106 mm x 58 mm
SCTxxxx

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sct6 seriesSct1 seriesSct2 seriesSct3 seriesSct7 seriesSct0 series ... Show all

Table of Contents