Beckhoff SCT Series Documentation page 32

Current transformers (ct) for energy measurement
Hide thumbs Also See for SCT Series:
Table of Contents

Advertisement

Technical data, functional description, installation
SCT2421 | Ring-type current transformer for primary currents 1250/1500 A, accuracy class 0.5
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 34] (W x H x D)
Approvals/markings
Versions
SCT2421-1250
SCT2421-1500
SCT2515 | Ring-type current transformers for primary current 2000 A, accuracy class 1
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 34] (W x H x D)
Approvals/markings
Versions
SCT2515-2000
SCT2525 | Ring-type current transformers for primary current 2000 A, accuracy class 0.5
Technical data
Accuracy class
Primary current
Secondary current
Max. diameter round conductor
Possible bar dimensions
Size
Dimensions [} 34] (W x H x D)
Approvals/markings
Versions
SCT2525-2000
32
current ratio 1250/1 A,
rated power 10 VA
current ratio 1500/1 A,
rated power 10 VA
current ratio 2000/5 A,
rated power 15 VA
current ratio 2000/5 A,
rated power 15 VA
Version: 1.1
SCT2421-xxxx
0.5
1250/1500 A
1 A
43.7 mm
50 x 30 mm, 63 x 10 mm
4
95 mm x 115 mm x 52 mm
CE
SCT2515-xxxx
1
2000 A
5 A
54.7 mm
60 x 30 mm, 80 x 10 mm
5
120 mm x 135 mm x 52 mm
CE
SCT2525-xxxx
0.5
2000 A
5 A
54.7 mm
60 x 30 mm, 80 x 10 mm
5
120 mm x 135 mm x 52 mm
CE
SCTxxxx

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sct6 seriesSct1 seriesSct2 seriesSct3 seriesSct7 seriesSct0 series ... Show all

Table of Contents