Dipswitch Sw1 - Normal Mode Diagnostic Port Characteristics; Inipt02 Dipswitch Sw1 Settings (Normal Operation); Inipt02 Dipswitch Sw1 Settings (Hardware Diagnostic Mode) - Bailey Infi 90 INIPR01 Instruction

Infi-net to plant loop remote interface
Table of Contents

Advertisement

INSTALLATION
Table 3-7. INIPT02 Dipswitch SW1 Settings (Normal Operation)
1,2
Pole
Setting
1
1
ROM checksumming disabled.
0
ROM checksumming enabled.
2
1
NIS handshake time-out disabled.
0
NIS handshake time-out enabled.
3
1
Unused.
0
Normal operating mode.
4
1
Normal mode diagnostic port (connector P4) enabled.
0
Normal mode diagnostic port (connector P4) disabled.
5/6
0/0
Normal mode diagnostic port baud rate of 1200.
0/1
Normal mode diagnostic port baud rate of 2400.
1/0
Normal mode diagnostic port baud rate of 9600.
1/1
Normal mode diagnostic port baud rate of 19200.
7/8
0/0
Normal mode diagnostic port data: 8 data bits, 1 stop bit, no parity.
0/1
Normal mode diagnostic port data: 8 data bits, 1 stop bit, even parity.
1/0
Normal mode diagnostic port data: 8 data bits, 1 stop bit, odd parity.
1/1
Normal mode diagnostic port data: 8 data bits, 2 stop bits, no parity.
NOTES:
1. 0 = CLOSED or ON, 1 = OPEN or OFF.
2. Shaded areas designate normal operating positions.
Table 3-8. INIPT02 Dipswitch SW1 Settings (Hardware Diagnostic Mode)
Pole
Setting
1
1
ROM checksumming disabled.
0
ROM checksumming enabled.
2
1
Single hardware diagnostic test execution.
0
Continuous hardware diagnostic test execution.
3 - 8
Hardware diagnostic tests (refer to Table
listing).
NOTE: 0 = CLOSED or ON, 1 = OPEN or OFF.
INIPT02 INFI-NET TO PLANT LOOP TRANSFER MODULE CONFIGURATION
3 - 12
DIPSWITCH SW1 - NORMAL MODE DIAGNOSTIC PORT
CHARACTERISTICS
Dipswitch SW1 is an eight-pole dipswitch that enables ROM
checksumming, enables NIS handshake time-outs, enables the
normal mode diagnostic port, sets the normal mode diagnostic
port communication rate, and sets the normal mode diagnostic
port data characteristics. Table
normal operation (pole one of dipswitch SW4 set to zero). Table
3-8
shows the pole settings for hardware diagnostic operation
(pole one of dipswitch SW4 set to one). Record the dipswitch
SW1 settings in the space provided.
Function
Function
3-7
shows the pole settings for
2
5-13
for a complete
User Setting
User Setting
I-E96-613A
®

Advertisement

Table of Contents
loading

Table of Contents