Eaton CurrentWatch ECSD Series Instruction Leaflet page 3

Current switches / dc current switches with jumper selectable current ranges

Advertisement

CurrentWatch™ ECSD Series Current Switches
DC Current Switches with Jumper Selectable
Current Ranges
Wiring Diagrams
Connect control or monitoring wires to the sensor. Use 12-22 AWG
copper wire and tighten terminals to 4.5 in.-lbs / 0.51 N·m maximum
torque. Be sure the output load does not exceed the switch rating.
CAUTION!
INCANDESCENT LAMPS CAN HAVE "COLD FILAMENT INRUSH" CURRENT OF
UP TO TEN TIMES THEIR RATED AMPERAGE. USE CAUTION WHEN SWITCHING
LAMP LOADS CONNECTED TO THE SOLID-STATE OUTPUT.
CAUTION!
DO NOT DISCONNECT OUTPUT TERMINALS UNDER LOAD.
Output
Diagram
Solid-State Output (N.O.)
Models
Mechanical Relay
(Form C) Models
Power Supply
Solid-State
12V AC/DC or 24V AC/DC
Output
1
2
Setpoint
Power Supply
Mechanical
12V AC/DC or 24V AC/DC
Relay Output
1
2
Setpoint
Instructions Publication P51991
Ranges and Maximum Amps
Range
Range
Maximum Amps
Jumper
Solid Core
5 sec.
Low
2-20 A
At least 1,000% of
range
Mid
10-50 A
High
15-100 A
Troubleshooting
Problem
Solution
Switch is
The jumper may be set in a range that is too low for current being moni-
always
tored. Move jumper to the correct range.
tripped.
The setpoint may be too low. Turn pot clockwise to increase setpoint.
Switch may have been overloaded and contacts are burned out. Check
the output load, remembering to include inrush on inductive loads (coils,
motors, ballasts).
Switch will
The jumper may be set in a range that is too high for current being
not trip.
monitored. Move jumper to the correct range.
The setpoint may be too high. Turn pot counter-clockwise to decrease
setpoint.
Unit might not be powered. Check power supply, power wiring, and
green Power LED on switch.
Switch may have been overloaded and contacts are burned out. Check
the output load, remembering to include inrush on inductive loads (coils,
motors, ballasts).
Specifications
Power Supply
12 VAC/DC (operates from 10-18 VAC/DC)
24 VAC/DC (operates from 20-28 VAC/DC)
Output Type and
Isolated Solid-State Output,
Rating
0.15 A @ 240 VAC/DC
Off-State Leakage
None
Repeatability
0.5%
Setpoint Range
2-20, 10-40, 40-100 A
Hysteresis
5% of Setpoint
Isolation Voltage
3 kV
Frequency Range
DC to 400 Hz
Sensing Aperture
0.75 in. (19 mm)
Housing
UL94 V0 Flammability Rated
Environmental
Operating Temperature:
-40 to +60°C (-40 to +140°F)
Approvals
UL Listed, E117028
UL Tested to Canadian Safety Standards
CE
RoHs Compliant
Effective July 2017
Continuous
At least 200% of range
indefinitely
Mechanical Relay (Form C),
5 A General Purpose @ 240 VAC,
3 A Inductive @ 240 VAC,
3 A @ 30 VDC,
1/8 HP @ 240 VAC
Operating Temperature:
-20 to +50°C (-4 to +122°F)
EATON www.eaton.com