Operation
7.3 Adjusting the differential
pressure set point of the
Type 2427 Actuator
(Type 42-37)
Î Before adjusting the differential pressure,
close the shut-off valve on the consumer
side or the bypass to reduce the maxi-
mum flow rate to approx. 5 %.
If you are using a motorized valve, close
it to approx. 10 % of its travel.
Î Set the differential pressure set point by
turning the set point adjuster (17) for dif-
ferential pressure counterclockwise ().
To do this, compare the pressures up-
stream and downstream of the consumer
at the reading of the installed pressure
gauges. If small differential pressure set
points are to be adjusted, we recom-
mend using a differential pressure gauge
instead of the two pressure gauges.
Turn the set point adjuster (17) clockwise ()
to increase the differential pressure set point
and counterclockwise () to reduce the dif-
ferential pressure set point.
7-6
7.4 Adjusting the pressure set
point of the Type 2429
Actuator (Type 42-39)
Adjust the pressure set point at the set point
adjuster (22) for pressure. While doing so,
observe the downstream pressure at the in-
stalled pressure gauge.
Turn the set point adjuster (22) clockwise ()
to increase the pressure set point and coun-
terclockwise () to reduce the pressure set
point.
EB 3017 EN