Mitsubishi Electric EcoMonitorPro EMU2-RD3-F Instruction Manual page 8

Energy measuring unit
Table of Contents

Advertisement

Below given is an example of connection for measurement of 2 transformer systems (differing in voltage and number of phases and wires) by
one unit (example of connection of EMU2-RD4-F-4W).
Circuit 1: primary voltage 63.5/110V, primary current 800A (EMU2-CT5-4W)-------800/5A current transformer is separately necessary.
Circuit 2: primary voltage 63.5/110V, primary current 250 A (EMU-CT250)
Circuit 3: primary voltage 254/440V, primary current 600 A (EMU-CT600)-----------
Circuit 4: primary voltage 254/440V, primary current 1000 A (EMU2-CT5-4W) -----
transformer are separately necessary.
EMU2-CT5-4W
63.5/110V
0
1
2
3
0
1
2
3
254/440V
Circuit 2
AC100
~220V
Circuit 1
CT
440
110
V
potential transformer is separately necessary.
3
3
440
110
V
potential
3
3
VT
440
110
3
3
(8/32)
transformer
and
1000/5A
Circuit 4
CT
EMU2-CT5-4W
Circuit 3
current