PMCSF6
OCCUPANCY SENSOR
Lens
Main Body
Power Cord
INTRODUCTION
The use of occupancy detectors in commercial and industrial applications can
significantly reduce energy usage lessening both energy costs and helping the
environment.
The PMCSF6 360 degrees MICRO SENSITIVE flush mount OCCUPANCY
DETECTOR uses passive infrared sensors (PIR) which react to changes in
temperature emitted by the slight motion of persons or objects passing through its
detection area. The PIR sensor automatically operates the connected load when
an area is occupied. After a preset time on non-activation (when an area is
vacated) the load will be switched off. In addition the built in photocell takes
natural light (daylight) into account when determining its activation.
Note: Read this entire manual before you start to install the system.
SAFETY PRECAUTIONS
Do not install when it may be possible for water to access the fitting.
Be sure to switch off power source before installing.
Make sure that the mains wiring comes from circuit with an external miniature
circuit breaker not higher than 10A for the short circuit protection or a suitable
fuse.
The unit should not be installed on the wall. (FIGURE 1)
IMPORTANT
Installation must be performed by a skilled/competent person who is familiar
with the appropriate standards and technical requirements of the appliance and
its proper installation.
Before proceeding with the installation, TURN OFF THE POWER TO THE
LIGHTING CIRCUIT AT THE CIRCUIT BREAKER OR FUSE BOX TO AVOID
ELECTRICAL SHOCK.
CHOOSING A MOUNTING LOCATION
Avoid aiming the motion sensor at heating vents, air conditioners or objects
which may change temperature rapidly.
Do not allow sunlight to fall directly on the front of unit.
The motion sensor is more sensitive to objects moving across its field of view.
It is less sensitive to an object moving directly towards the sensor head.
(FIGURE 2)
FIGURE 1
FIGURE 2

Advertisement

loading

Summary of Contents for E-matic PMCSF6

  • Page 1 CHOOSING A MOUNTING LOCATION The PMCSF6 360 degrees MICRO SENSITIVE flush mount OCCUPANCY Avoid aiming the motion sensor at heating vents, air conditioners or objects DETECTOR uses passive infrared sensors (PIR) which react to changes in which may change temperature rapidly.
  • Page 2: Installation

    INSTALLATION The unit has a sensing angle of 360°. It detects micro movement within a 6m diameter (sitting zone) and can detect general movement up to 10m diameter at a mounting height of 2.5 meters. (FIGURE 3) FIGURE 5 (4) In order to install the sensor to the ceiling, drill a diameter of 65mm round FIGURE 3 hole on the ceiling.
  • Page 3: Operation

    SETTING THE LIGHTING SYSTEM LUX ADJUSTMENT The LUX adjustment determines at what light level the light will start operating when you set the sensor to the AUTO MODE. (1) TEST MODE Turn the Lux control and the Time control counter-clockwise to the edge - the TEST position.
  • Page 4: Specifications

    Errors and omissions excepted. These instructions have been carefully checked prior to publication. However, no responsibility can be accepted by E-Matic for any misinterpretation of these instructions. Warning: Do not dispose of electrical appliances as unsorted municipal waste, use separate collection facilities.
  • Page 5 Model PMCSF6 Conditions : Maximum quantity of lamps listed below; Lighting Maximum Load For 2000W/8A(@240VAC) Lamp Q'ty x Watt Incandescent (CosΘ=1) 10x9W Lighting Maximum Load For 2000W/8A(@240VAC) 10x11W or 10x13W or 10x19W ; Halogen (CosΘ=1) Lighting Load (Number of fittings) for 10x20W or 10x23W ;...