Calibration Of The Operation Time - Emerson Bettis GVO LP DA Installation, Operation And Maintenance Manual

Double-acting pneumatic linear actuator
Table of Contents

Advertisement

Section 3: Operation and Use
October 2020
3.6

Calibration of the Operation Time

The calibration of the operation time is made by Emerson according to customer
requirements and to technical data-sheet included in technical documentation. If necessary
it's possible to modify or reset the operating time through the flow regulation valve placed
between the control valves enclosure and the pneumatic cylinder (Figure 17).
Figure 17
To carry out the adjustment, use an adequate Allen wrench and follow these steps (Figure 17):
22
Adjustment of Operation Time
Pneumatic connection
(Close) Screw for decrease speed
(Open) Unscrew for increase speed of operation
Loosen the lock nut.
Screw with a screwdriver the setting screw to increase the operation time.
Unscrew with a screwdriver the setting screw to decrease the operation time.
After the adjustment is over screw the lock nut.
Installation, Operation and Maintenance Manual
Pneumatic connection
Item 276: see operating diagram
Screwdriver
VCIOM-15792-EN Rev. 0