Table 3-5: Undervoltage Release
Control Voltages
Operational Voltage
Range 85-110%
1
24 Vdc
20-26 Vdc
1
27-35 Vdc
32 Vdc
1
41-53 Vdc
48 Vdc
1
110-125 Vdc
94-138 Vdc
1
220-250 Vdc
187-275 Vdc
2
94-140 Vac
110-127 Vac
2
208-240 Vac
177-264 Vac
2
380-415 Vac
323-457 Vac
2
408-528 Vac
480 Vac
2
600 Vac
510-660 Vac
1
Required for 200 ms
2
Required for 400 ms
Table 3-6: Auxiliary Switch, Overcurrent Trip Switch and
Cell Switch Contact Ratings
Control Voltages
Contact Rating Inductive Load
(amperes)
250 Vac
10
125 Vdc
0.5
250 Vdc
0.25
Table 3-7: Motor Operator
1
Control Voltages
Operational Voltage
Range 85-110%
24 Vdc
20-26
48 Vdc
41-53
110-125 Vdc
94-138
220-250 Vdc
187-225
110-127 Vac
94-140
208-240 Vac
177-264
1
AC voltages are 50/60Hz
1812.900A
Dropout Volts 30-
Inrush/Continuous Power
60%
Consumption
7-14 Vdc
250 W/18 W
10-19 Vdc
275 W/15 W
14-29 Vdc
275 W/18 W
33-75 Vdc
450 W/10 W
66-150 Vdc
450 W/10 W
33-76 Vac
450 VA/10 VA
62-144 Vac
400 VA/10 VA
114-249 Vac
480 VA/10 VA
144-288 Vac
400 VA/10 VA
180-360 Vac
400 VA/10 VA
Running
Typical Inrush Current
Current (A. avg.)
12.0
300% of Running
5.0
500% of Running
2.0
600% of Running
1.0
600% of Running
2.0
600% of Running
1.0
600% of Running
Opening Time
1 2
(ms)
70
70
70
70
70
70
70
70
70
70
Power Consumption
(watts or VA)
300
250
250
250
250
250
Magnum
Maximum Charging
Time (seconds)
5
5
5
5
5
5