BELT DEFLECTION FORCE - SEE TABLE 1
SET
SCREW
TORQUE ALL SHEAVE SET SCREWS TO 110-130 in. lbs
TABLE 1
BELT DEFLECTION FORCE (LBS)
BELT
SMALLEST
CROSS
SHEAVE
SECTION
DIAMETER
USED
3.0-3.6
A, AX
3.8-4.8
5.0-7.0
3.4-4.2
B, BX
4.4-5.6
5.8-8.6
TABLE 2
BELT CONDITION
TENSION FORCE IN BELT (LBS)
New
Used
Fig. 59 — V-Belt Force Label
BELT TENSION METHOD
Requires belt tension gage that measures tension in belt in units of
lbs force.
DEFLECTION = BELT SPAN
64
STRAIGHT
EDGE
SET
SCREW
UNNOTCHED
NOTCHED BELTS
BELTS
NEW
USED
NEW
3.7
5.5
4.1
4.5
6.8
5.0
5.4
8.0
5.7
—
—
4.9
5.3
7.9
7.1
10.5
6.3
9.4
8.5
12.6
100
80
MOUNTING
BOLTS (4)
6.1
7.4
Fig. 60 — Belt Drive Motor Mounting
8.4
Evaporator Coil Metering Devices
7.2
The metering devices are multiple fixed-bore devices (Acutrol™)
swedged into the horizontal outlet tubes from the liquid header, lo-
cated at the entrance to each evaporator coil circuit path. See
Fig. 61 and 62 for units with standard metering devices and
Fig. 63 for units with Humidi-MiZer
non-adjustable. Service requires replacing the entire liquid header
assembly. For more information, see the 50KC04-06 Service and
Maintenance Instructions.
Pre-Start and Start-Up
This completes the mechanical installation of the unit. Refer to the
unit's Service Manual for detailed Pre-Start and Start-Up instruc-
tions. Download the latest versions from HVAC Partners
(www.hvacpartners.com).
44
BLOWER PULLEY
V-BELT
MOTOR
PULLEY
MOTOR
MOTOR MOUNTING
PLATE
metering devices. These are
®