Belt Tension Method; Evaporator Coil Metering Devices; Pre-Start And Start-Up - Carrier 50KC04 Installation Instructions Manual

Single package rooftop cooling only with puron r-410a refrigerant
Table of Contents

Advertisement

BELT DEFLECTION FORCE - SEE TABLE 1
SET
SCREW
TORQUE ALL SHEAVE SET SCREWS TO 110-130 in. lbs
TABLE 1
BELT DEFLECTION FORCE (LBS)
BELT
SMALLEST
CROSS
SHEAVE
SECTION
DIAMETER
USED
3.0-3.6
A, AX
3.8-4.8
5.0-7.0
3.4-4.2
B, BX
4.4-5.6
5.8-8.6
TABLE 2
BELT CONDITION
TENSION FORCE IN BELT (LBS)
New
Used
Fig. 59 — V-Belt Force Label

BELT TENSION METHOD

Requires belt tension gage that measures tension in belt in units of
lbs force.
DEFLECTION = BELT SPAN
64
STRAIGHT
EDGE
SET
SCREW
UNNOTCHED
NOTCHED BELTS
BELTS
NEW
USED
NEW
3.7
5.5
4.1
4.5
6.8
5.0
5.4
8.0
5.7
4.9
5.3
7.9
7.1
10.5
6.3
9.4
8.5
12.6
100
80
MOUNTING
BOLTS (4)
6.1
7.4
Fig. 60 — Belt Drive Motor Mounting
8.4

Evaporator Coil Metering Devices

7.2
The metering devices are multiple fixed-bore devices (Acutrol™)
swedged into the horizontal outlet tubes from the liquid header, lo-
cated at the entrance to each evaporator coil circuit path. See
Fig. 61 and 62 for units with standard metering devices and
Fig. 63 for units with Humidi-MiZer
non-adjustable. Service requires replacing the entire liquid header
assembly. For more information, see the 50KC04-06 Service and
Maintenance Instructions.

Pre-Start and Start-Up

This completes the mechanical installation of the unit. Refer to the
unit's Service Manual for detailed Pre-Start and Start-Up instruc-
tions. Download the latest versions from HVAC Partners
(www.hvacpartners.com).
44
BLOWER PULLEY
V-BELT
MOTOR
PULLEY
MOTOR
MOTOR MOUNTING
PLATE
metering devices. These are
®