Step 9 - Units With Hinged Panels Only; Step 10 - Install External Condensate Trap; And Line - Carrier 50KC04 Installation Instructions Manual

Single package rooftop cooling only with puron r-410a refrigerant
Table of Contents

Advertisement

INDOOR
COIL
ACCESS
PANEL
Fig. 15 — Indoor Coil Access Panel Relocation
2.
Swing out indoor coil access panel and insert the hood sides
under the panel (hood top). Use the screws provided to attach
the hood sides to the hood top. Use screws provided to attach
the hood sides to the unit. See Fig. 16.
LEFT
HOOD
SIDE
19 1/16"
B
(483mm)
HOOD DIVIDER
Fig. 16 — Economizer Hood Construction
3.
Remove the shipping tape holding the economizer barometric
relief damper in place (economizer only).
4.
Insert the hood divider between the hood sides. See Fig. 16
and Fig. 17. Secure hood divider with 2 screws on each hood
side. The hood divider is also used as the bottom filter rack
for the aluminum filter.
5.
Open the filter clips which are located underneath the hood
top. Insert the aluminum filter into the bottom filter rack
(hood divider). Push the filter into position past the open filter
clips. Close the filter clips to lock the filter into place. See
Fig. 17.
6.
Caulk the ends of the joint between the unit top panel and the
hood top.
7.
Replace the filter access panel.
TOP
PANEL
TOP
PANEL
CAULK
HERE
INDOOR
COIL
ACCESS
PANEL
TOP
PANEL
INDOOR COIL
ACCESS PANEL
SCREW
33 3/8"
(848mm)
DIVIDER
BAROMETRIC
RELIEF
Fig. 17 — Economizer Filter Installation
Step 9 — Units with Hinged Panels Only
Relocate latch shipped inside the compressor compartment behind
the hinged compressor door to location shown in Fig. 18 after unit
installation.
If the unit does not have hinged panels, skip this step and continue
at Step 10.
COMPRESSOR
DOOR
Fig. 18 — Compressor Door Latch Location
Step 10 — Install External Condensate Trap

and Line

The unit has one
/
-in. condensate drain connection on the end of
3
4
the condensate pan and an alternate connection on the bottom. See
Fig. 19. Unit airflow configuration does not determine which
drain connection to use. Either drain connection can be used with
vertical or horizontal applications.
CONDENSATE PAN (SIDE VIEW)
STANDARD
SIDE DRAIN
Fig. 19 — Condensate Drain Pan (Side View)
To use the alternate bottom drain connection, remove the red drain
plug from the bottom connection (use a
extension) and install it in the side drain connection.
14
OUTSIDE
AIR
HOOD
CLEANABLE
ALUMINUM
FILTER
FILTER
FILTER
CLIP
OUTDOOR COIL
LATCH
ALTERNATE
DRAIN
PLUG
BOTTOM DRAIN
(FACTORY-INSTALLED)
/
-in. square socket drive
1
2