Device models

Following coupling decoupling network for signal and data lines exist:
Standard devices:
Model
Signal lines
CDN 118A-C4-4-1
CDN 118A-C6-4-1
3.2.

Impulse generators

The CDN 118A series can be used for the following surge generators:
Device
previous name
NSG 3040A
All models
NSG 3060A
All models
NSG 3040
All models
NSG 3060
All models
Operating manual
EUT max.
4 wires
50 VDC
4 wires
50 VDC
Pulseform
1.2/50s - 8/20s
1.2/50s - 8/20s
1.2/50s - 8/20s
1.2/50s - 8/20s
Test level max.
1A
4,8 kV 1.2/50us
1A
6,6 kV 1.2/50us
Remark generator
up to 4800V
up to 6600V
up to 4800V
up to 6600V
V 1.00
CDN 118A series
Coupling
gas arrestor or other
1.2/50µs
10/700µs
4 x 160 Ω
4 x 25 Ω
4 x 160 Ω
4 x 25 Ω
as per IEC 61000-4-5
as per IEC 61000-4-5
as per IEC 61000-4-5
as per IEC 61000-4-5