COMPONENT IDENTIFICATION
FRONT VIEW
RUN LED
ERR LED
• Pin Assignment
B
A
20
20
B
A
1
1
■ STATUS INDICATOR LED
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Bi-color (red/green) LED;
Red with input circuit abnormality (AD con-
verter response failure);
Green in normal operating conditions.
PC CONFIGURATOR
With configurator software, settings shown below are available.
Refer to the software manual of R3CON for detailed operation.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
Zero Scale
Full Scale
Zero Adjust
Full Adjust
Unused
Input Connector
AVAILABLE RANGE
-32000 to +32000
-32000 to +32000
-320.00 to +320.00
-32000 to +32000
0: Enable
1: Disable
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
SIDE VIEW
■ SIDE DIP SW
• Conversion Rate: SW3-1, 3-2
CONVERSION RATE
SW
40 ms
80 ms (*)
SW3-1
OFF
ON
SW3-2
OFF
OFF
(*) Factory setting
Note: Be sure to set unused SW3-3 and 3-4 to OFF.
DEFAULT SETTING
0
10000
0.00
1.0000
0: Enable
R3Y-DS8N
SW3
4
3
2
Conv.
1
Rate
ON
20 ms
10 ms
OFF
ON
ON
ON
EM-8968 Rev.3 P. 2 / 3