11. Safety devices

Type of protection
Circuit protection
Current fuse (Main PCB)
Fan motor
Thermal protection
protection
program
Terminal protection
program
(Compressor temp.)
Compressor
protection
Thermal protection
program
(Discharge temp.)
High pressure
Pressure switch
protection
Protection form
Activate
Reset
Activate
Reset
Activate
Reset
Activate
Reset
- 41 -
Model
AOYG09KXCA
250 V, 25 A
250 V, 5 A
250 V, 3.15 A
125 ±10 °C
Fan motor stop
120 ±10 °C
Fan motor restart
108 °C
Compressor stop
After 40 minutes
Compressor restart
110 °C
Compressor stop
After 7 minutes
Compressor restart
4.2 ±0.1 MPa
Compressor stop
3.2 ±0.15 MPa
Compressor restart
AOYG12KXCA
11. Safety devices