10. Electrical characteristics

Model name
Voltage
Power supply
Frequency
Max operating current *1
Starting current
Circuit breaker current
Power cable
Wiring spec. *2
Connection cable *3
Limited wiring length
*1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*2: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*3: Limit voltage drop to less than 2%. If voltage drop is 2% or more, increase cable conductor size.
AOYG09KXCA
V
Hz
A
14.0
A
5.1
A
16
2
2.5
mm
2
mm
m
- 40 -
AOYG12KXCA
230 ~
50
16.0
5.1
20
4.0
1.5
16