Capacity Compensation Rate For Pipe Length And Height Difference; Models: Aoyg09Kxca And Aoyg12Kxca - Fujitsu ASYG09KXCA Design & Technical Manual

Wall mounted type
Hide thumbs Also See for ASYG09KXCA:
Table of Contents

Advertisement

6. Capacity compensation rate for pipe length and height
difference
Indoor unit is higher than outdoor unit
Indoor unit
Connection pipe

6-1. Models: AOYG09KXCA and AOYG12KXCA

NOTE: Values mentioned in the table are calculated based on the maximum capacity.
Height difference H (m)
Height difference H (m)
6-1. Models: AOYG09KXCA and AOYG12KXCA
Height difference H
1
*
H
Outdoor unit
COOLING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
HEATING
Indoor unit is higher than
outdoor unit *1
Indoor unit is lower than
outdoor unit *2
- 35 -
Indoor unit is lower than outdoor unit
Outdoor unit
H
Indoor unit
Connection pipe
Pipe length (m)
5
7.5
10
-
7.5
-
0.960
5
0.992
0.964
0
1.000
0.972
-5
1.000
0.972
-7.5
-
0.972
-10
-
Pipe length (m)
5
7.5
10
-
7.5
-
0.994
5
1.000
0.994
0
1.000
0.994
-5
0.995
0.989
-7.5
-
0.987
-10
-

6. Capacity compensation rate for pipe length and height difference

2
*
10
15
-
0.929
0.872
0.933
0.876
0.937
0.879
0.944
0.887
0.944
0.887
0.944
0.887
-
0.944
0.887
10
15
-
0.968
0.890
0.968
0.896
0.968
0.896
0.968
0.986
0.963
0.891
0.961
0.889
-
0.959
0.887