Page 1
Power Quality Analyser UMG 604-PRO User manual and technical data Janitza electronics GmbH Vor dem Polstück 6 D-35633 Lahnau Support tel. +49 6441 9642-22 email: info@janitza.com www.janitza.com...
UMG 604-PRO www.janitza.de Safety Please read this user manual and all other 2. 1 Safety information publications that must be consulted to work Symbols used: with this product. This applies particularly This symbol is used as an addition to installation, operation and maintenance.
UMG 604-PRO www.janitza.de 2. 2 Safety measures 2. 3 Qualified staff When operating electrical devices, certain This device must only be operated and parts of these devices are invariably repaired by specialised personnel. subjected to hazardous voltage. Therefore, severe bodily injuries or damage to property...
UMG 604-PRO www.janitza.de Proper use NOTE! 3. 1 Inspection on receipt The user manual also describes The prerequisites of faultless, safe operation options that are not supplied as of this device are proper transport and proper standard. storage, set-up and installation, as well as careful operation and maintenance.
4. 4 GridVis® network analysis software use in industrial areas. You can use the GridVis® network analysis software that is available at www.janitza.de to 4. 1 Measuring process program the device and read out data. To do The device measures continuously and...
UMG 604-PRO www.janitza.de 4. 5 Features General • Installation on a 35 mm DIN rail • LCD display, backlight (optional) • Operation via 2 buttons • 4 voltage and 4 current measurement inputs • 1 temperature measurement input • 2 digital outputs and 2 digital inputs •...
DIN 43880 It is assembled on a 35 mm mounting rail in accordance with DIN EN 60715. It can be installed in any position. Fig. Front view of UMG 604-PRO on mounting rail...
UMG 604-PRO www.janitza.de Network systems Suitable network systems and maximum rated voltages (DIN EN 61010-1/A1): Three-phase four- Three-phase four- Three-phase three- Three-phase three- conductor systems conductor systems conductor systems conductor systems with earthed neutral with non-earthed neutral not earthed with earthed phase...
Earthing of Voltage measurement the system Fig. Schematic diagram, UMG 604-PRO in an IT Auxiliary supply UMG604-PRO network without N. Fig. Schematic diagram, UMG 604-PRO in a TN network 230/400 V 50/60 Hz Impedance AC/DC Earthing of the system Voltage measurement...
UMG 604-PRO www.janitza.de 5. 3 Rated voltages The following illustrations show lists of networks and the corresponding rated network voltages in which the device can be 115V used. 120V 127V 200V 230V 240V 66 V / 115 V 260V 120 V / 208 V...
UMG 604-PRO www.janitza.de Installation 6. 1 Disconnectors Damage to property due During building installation, provide a suitable to not observing the CAUTION! disconnector in order to disconnect the connection conditions device from the current and voltage. Failure to observe the connection conditions can damage or destroy your device.
UMG 604-PRO www.janitza.de 6. 3 Measured voltage The device is designed to measure AC voltage in 300 V networks, in which overvoltages of category III can occur. The device can only determine measured values if measured voltage of >10 Veff is present on at least one voltage measurement input.
UMG 604-PRO www.janitza.de 6. 4 Current measurement Risk of injury due to elec- The device: tric voltage on current WARNING! • is intended for connecting current transformers! transformers with secondary currents of On current transformers that are operated open ../1 A and ../5 A.
UMG 604-PRO www.janitza.de 6. 4. 1 Ammeter 6. 4. 2 Total current measurement If you wish to measure the current not only For a summation measurement via with the UMG but rather with an ammeter two current transformers, first set their too, connect the ammeter to the UMG in total transformation ratio on the device.
UMG 604-PRO www.janitza.de 6. 5 Connection variants 6. 5. 1 Voltage measurement Fig. Connection examples for voltage measurement in “Three-phase 4-conductor networks” and “Single-phase 3-conductor networks”. Fig. Connection examples for voltage measurement in “Three-phase 3-conductor networks”.
UMG 604-PRO www.janitza.de 6. 5. 2 Current measurement 3p 4w 3p 2i Fig. Current measurement, connection example for Fig. Current measurement, connection example for connection variant 0. connection variant 0. 2p 2i0 1p 2i Fig. Current measurement, connection example for Fig.
UMG 604-PRO www.janitza.de NOTE! 6. 5. 3 Supporting measurement, input V4 If the baseline measurement (inputs V1-V3) is connected to a three-phase 4w 1m 3-conductor network, the supporting measurement (input V4) can no longer be used as a measurement input.
UMG 604-PRO www.janitza.de 6. 6 Temperature measurement Transmission errors and The device has a temperature measurement damage to property due CAUTION! input that is designed for a maximum total to electrical faults burden of 4 kOhm. The total burden refers to sensors and the line.
UMG 604-PRO www.janitza.de Interfaces Risk of injury due The device has the following interfaces: to electric voltage! WARNING! • RS232 RS232, RS485 and the temperature • RS485 measurement input are not galvanically • Ethernet separated from each other. The Profibus •...
UMG 604-PRO www.janitza.de 7. 2 RS232 7. 3 RS485 You can use an RS232 connection cable to The RS485 interface is designed as a 2-pin connect the device to a PC. plug contact in the UMG 604. The achievable distance between two...
UMG 604-PRO www.janitza.de 7. 3. 2 Cable type CAT cables are not suitable for bus wiring. 7. 3. 1 Termination resistors Instead, we recommend the following cable The cable is terminated with resistors (120 Ohm 1/4 W) at the beginning and at the end of a segment.
UMG 604-PRO www.janitza.de 7. 4 Bus structure • All devices are connected in a bus • If the master is replaced with a bus structure (line). connection, the bus must be switched off. • Up to 32 participants can be connected •...
Phoenix. If there are no subsequent devices in the line, the bus wiring must be terminated with a You can order this from us using Janitza item resistor (switch to ON). With the switch set to number 13.10.539.
UMG 604-PRO www.janitza.de Digital inputs and outputs 8. 1 Digital inputs Transmission errors and The device has 2 digital inputs to which you damage to property due to CAUTION! can connect one signal generator each. electrical faults If the line is longer than 30 m, there is...
Fig. UMG 604-PRO with inputs for 24V. Example with S0 pulse transducer. Digital Input 1 3.9V S0 pulse Digital transducer Input 2 3.9V 4k 1.5k Fig. UMG 604-PRO with inputs for 24V and an S0 pulse transducer on digital input 2.
UMG 604-PRO www.janitza.de 8. 3 Digital outputs Transmission errors and The device has 2 transistor switching outputs damage to property due to CAUTION! that are galvanically separated from the electrical faults analysis electronics using opto couplers. If the line is longer than 30 m, there is...
UMG 604-PRO www.janitza.de Commissioning Before commissioning, clear any content 9. 3 Connecting the measured voltage that may be present on the power meters, The device is suitable for measuring voltages min./max. values or recordings due to the of up to 300VAC to earth and 520 V AC production process.
UMG 604-PRO www.janitza.de 9. 5 Applying the measured current 9. 6 Checking the power measurement The device: Short-circuit all current transformer outputs • is intended for connecting current except for one and check the displayed transformers with secondary currents of power outputs.
UMG 604-PRO www.janitza.de Operation In order to make it easier to install and 10. 2 Display mode commission the device without a PC, it has After the power returns, the device is in a display, as well as buttons 1, 2 and Service.
UMG 604-PRO www.janitza.de 10. 3 Programming mode 10. 4 Display password You view and change the most important To make it harder to accidentally modify the settings required to operate the device in programming data on the device, you can programming mode.
UMG 604-PRO www.janitza.de Configuration This section describes how to perform 11. 2 Current connection variants configuration using the 2 buttons on the The device recognises two connection device. variants for current measurement. 11. 1 Current transformer ratio Connection variant 0 You can assign each of the 4 current •...
UMG 604-PRO www.janitza.de 11. 3 Voltage transformer ratio 11. 4 Voltage connection variants You can assign each of the 4 voltage The device recognises two connection transformer inputs its own voltage variants for voltage measurement. transformer ratio. Connection variant 0 •...
UMG 604-PRO www.janitza.de 11. 5 RS232 configuration 11. 6 RS485 configuration The following data must be programmed to The following data must be programmed to operate the RS232 interface: operate the RS485 interface: • baud rate, • device address, • operating mode.
Patch cable Patch cable Switch Patch cable Patch cable Switch Fig. Connection example, the UMG 604-PRO and PC Fig. Connection example, the UMG 604-PRO and PC are require a static IP address. automatically assigned an IP address by a DHCP server.
The device master file for your device number of the is called “0B41.GSD” and is Profibus profile requested by the UMG. available on the Janitza homepage. In order to request a Profibus profile, write the profile number in the first byte in the PLC output box.
UMG 604-PRO www.janitza.de 11.8.3 Pre-set profiles Profibus profile number 0 Voltage L1-N Float Voltage L2-N Float Voltage L3-N Float Voltage L4-N Float Voltage L2-L1 Float Voltage L3-L2 Float Voltage L1-L3 Float Current L1 Float Current L2 Float Current L3 Float...
Page 48
UMG 604-PRO www.janitza.de Profibus profile number 1 Voltage L1-N Float Voltage L2-N Float Voltage L3-N Float Voltage L2-L1 Float Voltage L3-L2 Float Voltage L1-L3 Float Current L1 Float Current L2 Float Current L3 Float Active power L1 Float Active power L2...
Page 49
UMG 604-PRO www.janitza.de Profibus profile number 2 Total active energy L1-L3 Float Rel. Total active energy L1-L3 Float Deliv. Total active energy L1-L3 Float Total reactive energy L1-L3 Float Ind. Total reactive energy L1-L3 Float Total cap. reactive energy L1-L3...
UMG 604-PRO www.janitza.de 11. 9 Recording configuration Recording 2 2 recordings are pre-configured in the device’s factory default setting. The following measured values are recorded with the time base of 1 hour: Recordings are adjusted and expanded using the GridVis® software.
· In the GridVis software (device configuration). · Via the parameter _MODE_NTP (the Modbus address can be found in the Modbus address list of your device at www.janitza.de). 11.10.1 Important Modbus parameters for the PTP configuration of the device Modbus parameters have the following meaning:...
INFORMATION · A Modbus address list including all the PTP parameters of your device can be found in the download area at www.janitza.de. · Specifications for PTP (Precision Time Protocol) can be found in IEEE Standard for a Precision Clock Synchronization Protocol for Networked Measurement and Control Systems (IEEE Std.
UMG 604-PRO www.janitza.de System information 12. 1 Measurement range exceeded Serial number If the measurement range is exceeded, it is displayed as long as this persists and cannot be acknowledged. The measurement range is exceeded if at least one of the four voltage or current measurement inputs is outside its specified metering range.
UMG 604-PRO www.janitza.de Device homepage Your measurement device has an integrated You can do the following here without first web server, which has a separate homepage. installing any software: You can use this device home page to access • call historical and current measured your measurement device from any end device values.
UMG 604-PRO www.janitza.de 13. 1 Measured values You can use the Measured values menu item to call simple and detailed views of the measured values, and to display individual measured values. The following menu items are available: • Short overview •...
UMG 604-PRO www.janitza.de 13. 1. 2 Detailed measured values In the overview, you can call extensive information on the following points: • Voltage • Current • Power • Harmonic oscillations • Energy • Peripheral devices (digital inputs/outputs, temperature measurements) Fig. Detailed overview of measured values...
UMG 604-PRO www.janitza.de 13. 1. 3 Diagrams You can use the “Diagrams” item to access the measured values monitor. The measured val- ues monitor is a configurable display of current and historical measured values with automatic scaling. In order to display a graphic of the measured values, drag the required values from the list on the left edge of the screen into the field in the middle of the screen.
UMG 604-PRO www.janitza.de 13. 1. 5 Transients The “Transients” area provides a graphic illustration of transients within a date list. Transient voltages: • are fast impulse transient effects in electrical networks. • are unpredictable from a time perspective and have a limited duration.
UMG 604-PRO www.janitza.de 13. 2 Power quality The “Power quality” section (PQ) provides you with the option of calling the PQ status in a clear way according to common standards. Here, you have access to permanent power quality monitoring in accordance with: •...
UMG 604-PRO www.janitza.de 13. 3 Apps You have the option of extending the functions on your device retrospectively by installing additional apps. 13. 3. 1 Push Service The push service is an example of an installable app. The push service sends measured...
You can use the Device information menu item to obtain all information and settings that you can change on the device. 13. 4. 2 Downloads You can use the Downloads item to access the download area on the Janitza homepage. You can download catalogues, operation manuals and additional documentation from here. 13. 4. 3 Display The Display item provides you with the display of your device, which corresponds to the real display.
UMG 604-PRO www.janitza.de Service and maintenance The device underwent various safety checks 14. 5 Battery before delivery and is marked with a seal. The internal clock is fed from the supply If a device is open, the safety checks must voltage.
UMG 604-PRO www.janitza.de Procedure in the event of faults Possible fault Cause Remedy No display External fuse for the power Replace fuses. supply voltage has tripped. Device defective. Send the device to the manufacturer for repair. No current display Measured voltage is not Connect the measured voltage.
Page 67
UMG 604-PRO www.janitza.de Possible fault Cause Remedy “Error CF” on the The calibration data could not Send the device to the display be read. manufacturer for inspection and testing along with an accurate fault description. Active power, At least one current transformer...
UMG 604-PRO www.janitza.de Technical data 16. 1 General Net weight 350 g (0.771 lb) Device dimensions Approx. l=107.5 mm (4.23 in), w=90 mm (3.54 in) h=82 mm (3.23 in) (per DIN 43871:1992) Housing flammability rating UL 94V-0 Installation position Fastening/assembly...
UMG 604-PRO www.janitza.de 16. 4 Supply voltage The supply voltage must be connected through a UL/IEC approved fuse (6A char. B) to the device. 230 V option: • Nominal range 95 V to 240 V (50/60 Hz) / DC 135 V to 340 V •...
UMG 604-PRO www.janitza.de 16. 6 Digital inputs and outputs Digital inputs Maximum counter frequency 20 Hz (Pulse input S0) Switching input Input signal present 18 V to 28 V DC (typical 4 mA) Input signal not present 0 to 5 V DC, current less than 0.5 mA...
UMG 604-PRO www.janitza.de 16. 7 Temperature measurement input Temperature measurement input 3-wire measurement Update time Approx. 200 ms Connectable sensors PT100, PT1000, KTY83, KTY84 Total burden (sensor + cable) max. 4 kOhm Cable length up to 30 m (32.81 yd) unshielded, from 30 m (32.81 yd) shielded...
UMG 604-PRO www.janitza.de 16. 8 Voltage measurement inputs Three-phase 4-conductor systems (L-N/L-L) max. 277 V / 480 V Three-phase 3-conductor systems (L-L) max. 480 V Resolution 0.01 V Metering range L-N to 600 Vrms Metering range L-L to 1000 Vrms...
UMG 604-PRO www.janitza.de Terminal connection capacity (current measurement) Conductors to be connected. Only one conductor can be connected per terminal! Single core, multi-core, fine-stranded 0.08 - 4.0 mm , AWG 28-12 Cable end sleeve (not insulated) 0.25 - 4.0 mm...
• Comparator timer • S0 counter statuses • Min. / Max. / mean values (without the date and time) • Energy values Configuration data is saved immediately. A detailed Modbus address and parameter list can be found at www.janitza.com...
UMG 604-PRO www.janitza.de Parameter list Address Designation Setting range Unit Default Current transformer, primary, L1 to L4 0 to 1000000 Current transformer, secondary, L1 1 to 5 to L4 Voltage transformer, primary, L1 to L4 0 to 1000000 Voltage transformer, secondary, L1...
Page 77
UMG 604-PRO www.janitza.de Address Designation Setting range Unit Default Collect TFTP configuration file 0 to 9999 automatically 0 = deactivated x = file number TFTP error handling 0 to 1 0 = in the event of an error, the configuration menu is shown on the display.
Page 78
UMG 604-PRO www.janitza.de Address Designation Setting range Unit Default Device address, Modbus/Profi- 1 to 255 Baud rate, RS232 0 to 4 0 = 9600Bit/s 1 = 19200Bit/s 2 = 38400Bit/s 3 = 57600Bit/s 4 =115200Bit/s Baud rate, RS485 0 to 5...
Page 79
UMG 604-PRO www.janitza.de Address Designation Setting range Unit Default 1 to 31 Month 1 to 12 Year 1 to 9999 xxxx Hour 0 to 23 Minute 0 to 59 Second 0 to 59 Copy date and time 0, 1 1 = copy set data...
UMG 604-PRO www.janitza.de Measured value indications You can use buttons 1 and 2 on the display to display the following measured values in the factory default setting. The measured value designations used are abbreviated and have the following meanings: • Active power = active power, consumption •...
Page 82
UMG 604-PRO www.janitza.de Dimension diagrams 19. 1 Front view Fig. Front view of UMG 604-PRO with installation dimensions...
Page 83
UMG 604-PRO www.janitza.de 19. 2 Side view Fig. Schematic side view of UMG 604-PRO with installation dimensions...
Page 84
UMG 604-PRO www.janitza.de Connection example An. In RS232 RS485 Dig. I/O Versorgungs- spannung Auxiliary Supply Power Analyser UMG 604-PRO Strommessung Spannungsmessung Current measurement Voltage measurement Fig. Connection example for UMG 604-PRO...
Page 86
1 and 2 simultaneously for approximately one second. • The symbol for programming mode PRG Fig. UMG 604-PRO display in programming mode appears. • The contents of address 000 are displayed. 2. Enter the primary current by using button 1 to select the number to be changed and button 2 to change the selected number.
Page 87
UMG 604-PRO www.janitza.de FCC Compliance Statement This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful inter- ference in a residential installation.