Rotary switch S1 for subscriber number addressing
Fig. 17
Configuring functions
Set the connected function during commissioning of
the heat generator.
Setting for the connected function in the commissioning assistant:
Function
External functions
External default set flow temperature
■
External default output
■
Operating mode changeover
■
External demand
■
External blocking
■
Fault message input and fault message output
Connection without system blocking
■
Connection with system blocking, 230 V
■
Connection with system blocking, 24 V
■
Connecting only message facility (e.g. buzzer)
■
External LPG valve
External extractor interlock
Commissioning and adjustment
Set rotary switch S1 to a consecutive numbers as
shown in the example below:
■
1st EM-EA1 extension: Rotary switch to 1
■
2nd EM-EA1 extension: Rotary switch to 2
■
3rd EM-EA1 extension: Rotary switch to 3
Note
These settings are independent of the settings made
at other extensions, such as EM-MX (mixer). If an
EM-EA1 extension (DIO electronics module) has the
setting 1, an EM-MX, EM-M1 or EM-P1 extension
(ADIO electronics module) can also have the setting 1.
Commissioning assistant
Heat generator installation and service instruc-
tions
Setting
"External set flow temperature 0 to 10 V"
"External default output 0 to 10 V"
"Operating mode changeover"
"External demand"
"External blocking"
"Fault message input 230 V and fault message out-
put"
"Fault message input 230 V and block system"
"Fault message input 24 V and block system"
"Fault message output 230 V"
"LPG valve"
"Cooker hood"
17