SMA Sunny Island 6.0H System Description page 10

Multicluster systems with stand-alone grid or increased self-consumption and battery-backup function
Hide thumbs Also See for Sunny Island 6.0H:
Table of Contents

Advertisement

2 Safety
Danger to life from electric shock due to circuit breakers that cannot be tripped
In off-grid systems and battery-backup systems, the Sunny Island can only trip circuit breakers up to a certain
tripping characteristic. Circuit breakers with a higher operating current cannot be tripped. Under fault conditions, a
voltage that poses a danger to life may be present on accessible parts for several seconds. Touching live
components can result in death or serious injury due to electric shock.
• SI6.0H-13 and SI8.0H-13: Check whether a circuit breaker has a higher trip characteristic than B16 (B16A) or
C6 (C6A).
• If a circuit breaker has a higher trip characteristic than the specified circuit breakers that can be tripped, you
should also install a residual-current device of type A.
Risk of crushing injuries due to moving PV array parts
A generator can be started automatically by the Sunny Island. Moving parts in the PV array can crush or sever
body parts.
• Operate the generator only with the specified safety equipment.
• Carry out all work on the generator in accordance with the manufacturer's specifications.
Risk of burns due to short-circuit currents on the disconnected inverter
The capacitors in the DC input area of the inverter store energy. After the battery is isolated from the inverter,
battery voltage is still temporarily present at the DC terminal. A short circuit at the DC terminal of the inverter can
lead to burns and may damage the inverter.
• Wait 15 minutes before performing any work at the DC terminal or on the DC cables. This allows the
capacitors to discharge.
Risk of burns due to hot enclosure parts
Some parts of the enclosure can get hot during operation.
• Mount the inverter in such a way that it cannot be touched inadvertently during operation.
Damage to the system due to sand, dust and moisture ingress
Sand, dust and moisture penetration can damage the system and impair its functionality.
• Only open the product if the humidity is within the thresholds and the environment is free of sand and dust.
• Do not open the product during a dust storm or precipitation.
Damage to the inverter due to electrostatic discharge
Touching electronic components can cause damage to or destroy the inverter through electrostatic discharge.
• Ground yourself before touching any component.
10