Bailey INFI 90 Instruction page 49

Infi-net to computer interfaces
Hide thumbs Also See for INFI 90:
Table of Contents

Advertisement

TROUBLESHOOTING
INICT01 AND INICT03 MODULE ERROR CODES
Table 5-2. INICT01 and INICT03 Module Error Codes
LED
Code
8 7 6 5 4 3 2 1
0D
0 0 0 0 1 1 0 1
12
0 0 0 1 0 0 1 0
13
0 0 0 1 0 0 1 1
19
0 0 0 1 1 0 0 1
31
0 0 1 1 0 0 0 1
32
0 0 1 1 0 0 1 0
33
0 0 1 1 0 0 1 1
34
0 0 1 1 0 1 0 0
35
0 0 1 1 0 1 0 1
36
0 0 1 1 0 1 1 0
39
0 0 1 1 1 0 0 1
3F
0 0 1 1 1 1 1 1
NOTE: 0 = LED OFF, 1 = LED ON.
1. Codes are displayed only when the ICT module is halted and the status LED is red.
INICT01 AND INICT03 MODULE ERROR CODES
5 - 2
If errors occur while the ICT module is operating, the status
LED turns red and the CPU LEDs on the ICT module faceplate
display error codes. Table
and associated corrective action. The ICT module displays error
codes only when it is halted. Five status bytes provide informa-
tion about the ICT module status. Tables 5-3, 5-4, and
the NIS module edge connector pin assignments. Tables 5-6,
5-7, and
5-8
list the INICT01 module edge connector pin
assignments. Tables 5-9, 5-10, and
ule edge connector pin assignments. Tables
the IMMPI01 module edge connector pin assignments.
A code that is not on the list may appear if a machine fault
time-out occurs. Reset the ICT module if this happens. The ICT
module has failed if the status LED remains red. Replace the
ICT module in this case.
Condition
I/O expander bus errors
NIS module not responding
ROM checksum error
SCSI port error
(INICT03 only)
Memory or CPU fault
Address or bus error
Illegal instruction
Trace/privilege violation
Spurious/unassigned
exception
Divide by zero/checksum/
format error
Duplicate node number on loop
The ICT module has stopped
because the user pressed the
stop pushbutton
5-2
lists the ICT module error codes
5-11
list the INICT03 mod-
5-12
Corrective Action
Check I/O expander bus for
connections to other modules.
Replace NIS module.
Replace NIS module
Replace NIS module, check cabling and
termination unit
Replace ICT module
Reset ICT module, replace ICT module if
error continues
Change node number
Reset ICT module
5-5
list
and
5-13
list
I-E96-610A
®

Advertisement

Table of Contents
loading

This manual is also suitable for:

Infi-net inici01Infi-net inici03

Table of Contents