Bailey INFI 90 Instruction page 37

Infi-net to computer interfaces
Hide thumbs Also See for INFI 90:
Table of Contents

Advertisement

INSTALLATION
WARNING
AVERTISSEMENT
INICT01 MODULE INSTALLATION
3 - 12
Disconnect power before installing dipshunts on the module
mounting unit backplane. Failure to do so will result in contact
with cabinet areas that could cause severe or fatal shock.
Interrompez l'alimentation avant d'installer des dipshunts sur
le fond de panier du châssis de montage des modules. Sinon,
tout contact avec cette zone entraîne des risques d'lectrocu-
tion sérieuse ou fatale.
2. Verify that a 24-pin dipshunt is installed in the I/O
expander bus sockets between the module mounting unit slot
to be used by the NIS module and the slot to be used by the ICT
module.
NOTE: When installing the NIS module with an ICT module, there
must be continuity between the NIS module and the CPU circuit
board of the ICT module. Observe the following:
a.
Install one dipshunt in the I/O expander bus socket between the NIS
slot and ICT slot if the NIS module is mounted to the left of the ICT
module.
b.
If the NIS module is mounted to the right of the ICT module, two dip-
shunts are required. Install one dipshunt between the NIS slot and ICT
slot. Install the second dipshunt between the slots of the memory circuit
board and the CPU circuit board of the ICT module.
3. Remove any 24-pin dipshunts from the I/O expander bus
sockets that would connect the INICT01 module to any module
other than the NIS module.
4. Attach the hooded end of the NKTU01, NKTU02, NKTU11,
or NKTU12 cable to the module mounting unit backplane cable
connector opening for the ICT module. The other end of the
cable attaches to the termination device or to the termination
mounting unit backplane.
5. Slide the ICT module in while guiding the top and bottom
edges of the circuit boards along the top and bottom rails of the
module mounting unit.
6. Push on the faceplate until the rear edges of the module are
firmly seated in the backplane connectors.
7. Turn the 2 latch screws ½ turn to lock the module in place.
The module is locked into place when the open end of the slot
on the latching screws face the center of the faceplate.
Refer to the NTMF01 termination unit or NIMF01 and NIMF02
termination module instruction for complete termination
device information.
Appendix C
information about these termination devices.
and
D
provide quick reference
®
I-E96-610A

Advertisement

Table of Contents
loading

This manual is also suitable for:

Infi-net inici01Infi-net inici03

Table of Contents