Vollrath 9718C-1-VCL Operator's Manual page 4

Down draft vent module with induction range(s)
Table of Contents

Advertisement

Available languages

Available languages

FIRE SUPPRESSION SYSTEM INSTALLATION
WARNING
Fire, Injury, Death Hazard
This equipment must installed and adjusted by a qualified
technician in accordance with all federal, state and local codes.
Failure to install adjust or maintain this equipment properly can
result in property damage, injury or death.
NOTICE: The ANSUL Fire Suppression System must be charged by
an authorized ANSUL representative. The Downdraft Vent
Module will not operate and cooking appliance will not be
energized until the ANSUL Fire Suppression System has
been charged.
NOTICE: It is the installer's responsibility to verify that this
equipment installation is in compliance with the
specifications listed in this manual, ANSUL
documentation, local code requirements, and NFPA
standards.
The following instructions are for use only by authorized ANSUL representatives. Refer to ANSUL documentation for the following steps.
ANSUL representative to supply:
• CO
or nitrogen cartridge
2
• ANSULEX Low pH Liquid Fire Suppressant
Fusible Links and Gas Cartridges
A
ANSUL Model SL Fusible Link 165° F
B
LT-20-R Cartridge
1. Replace the four temporary test links with the supplied 165°F SL
Fusible Links. Refer to Particulate Filter Replacement on page 6 for
instructions for removing the particulate filters.
2. Install the CO
or nitrogen cartridges onto the ANSUL automatic
2
release/bracket assembly.
4
A
A
A
B
Down Draft Vent Module with Induction Range(s) Operator's Manual
Fire Extinguishing Tank and Nozzles
A
A
ANSUL R-102 1W Nozzle (Appliance)
B
ANSUL R-102 1W Nozzle (Duct)
C
ANSUL R-102 1¹⁄₂ Gallon Tank
Fill the agent tank with ANSULEX low pH Liquid Fire Suppressant.
A
B
B
C

Advertisement

Chapters

Table of Contents
loading

Table of Contents