Preface This document is the original document. All rights to this documentation are reserved by Pilz GmbH & Co. KG. Copies may be made for the user's internal purposes. Suggestions and comments for improving this documenta- tion will be gratefully received.
Function Description Installation Wiring Preparing for operation Operation Status indicators Faults – Interference Dimensions in mm Technical details Safety characteristic data Supplementary data Service life graph Remove plug-in terminals Order reference EC declaration of conformity Operating Manual PNOZ po3.1p 20676-EN-07...
PNOZ po3.1p Introduction Validity of documentation This documentation is valid for the product PNOZ po3.1p. It is valid until new documenta- tion is published. This operating manual explains the function and operation, describes the installation and provides guidelines on how to connect the product.
Safety Intended use The PNOZ po3.1p is an expansion module of the safety system PNOZpower. It may only be used with a base unit or a control module of the modular safety system PNOZpower. The expansion module meets the requirements of EN 60947-5-1, EN 60204-1 and VDE 0113-1.
Note for overvoltage category III: If voltages higher than low voltage (>50 VAC or >120 VDC) are present on the unit, connected control elements and sensors must have a rated insulation voltage of at least 250 V. Operating Manual PNOZ po3.1p 20676-EN-07...
Fit the unit to a horizontal DIN rail. If other mounting positions are used, the switching capability values stated in the technical details cannot be maintained. There are 2 sockets on the rear of the PNOZ po3.1p. The base unit/control module and the expansion modules are connected using the jumpers supplied.
Sufficient fuse protection must be provided on all output contacts with capacitive and in- ductive loads. Do not switch low currents using contacts that have been used previously with high cur- rents. Ensure the wiring and EMC requirements of EN 60204-1 are met. Operating Manual PNOZ po3.1p 20676-EN-07...
The safety functions may only be checked by qualified personnel. Status indicators LEDs indicate the status and errors during operation: LED on POWER Supply voltage is present. CH.1 Safety contacts of channel 1 are closed. Operating Manual PNOZ po3.1p 20676-EN-07...
Page 11
PNOZ po3.1p CH.2 Safety contacts of channel 2 are closed. FAULT Contact malfunction Operating Manual PNOZ po3.1p 20676-EN-07...
CCC, CE, EAC (Eurasian), TÜV, cULus Listed Electrical data Supply voltage Voltage 24 V Kind Power consumption Duty cycle 100 % Relay outputs Number of output contacts Safety contacts (N/O), instantaneous Utilisation category In accordance with the standard EN 60947-4-1 Operating Manual PNOZ po3.1p 20676-EN-07...
Page 13
Conv. therm. current with 6 contacts 5,8 A Conv. therm. current with 7 contacts 5,4 A Conv. therm. current with 8 contacts Times Switch-on delay With automatic start typ. 30 ms With automatic start max. 50 ms Operating Manual PNOZ po3.1p 20676-EN-07...
Page 14
0,25 - 2,5 mm², 24 - 14 AWG 2 core with the same cross section, flexible without crimp connectors or with TWIN crimp connectors 0,5 - 1,5 mm², 24 - 14 AWG Torque setting with screw terminals 0,5 Nm Operating Manual PNOZ po3.1p 20676-EN-07...
If the service life graphs are not accessible, the stated PFH value can be used irrespective of the switch frequency and the load, as the PFH value already considers the relay's B10d value as well as the failure rates of the other components. Operating Manual PNOZ po3.1p 20676-EN-07...
To increase the service life, sufficient spark suppression must be provided on all output contacts. With capacitive loads, any power surges that occur must be noted. With DC con- tactors, use flywheel diodes for spark suppression. Operating Manual PNOZ po3.1p 20676-EN-07...
The plug-in connection terminals should only be connected and disconnec- ted when the voltage is switched off. Order reference Product type Connection type Order No. PNOZ po3.1p Screw terminals 773 630 Operating Manual PNOZ po3.1p 20676-EN-07...
European Parliament and of the Council. The complete EC Declaration of Conformity is available on the Internet at www.pilz.com/support/downloads. Representative: Norbert Fröhlich, Pilz GmbH & Co. KG, Felix-Wankel-Str. 2, 73760 Ost- fildern, Germany Operating Manual PNOZ po3.1p...
Page 19
Back cover Support Technical support is available from Pilz round the clock. Americas Australia Scandinavia +45 74436332 Brazil +61 3 95600621 +55 11 97569-2804 Spain Canada Europe +34 938497433 +1 888-315-PILZ (315-7459) Austria Switzerland Mexico +43 1 7986263-0 +41 62 88979-30...