6.6 Cable sizing

Grundfos can supply submersible drop cables for
any type of installation.
The cross-section of the submersible drop
cable must be large enough to meet the
voltage requirements specified in section
5.1
General.
The table values below are calculated from the
following formula:
I x 2 x 100 x PF x L x ρ
q =
U x ΔU
Cross-section of submersible drop cable
q
=
2
[mm
].
I
= Rated maximum current of the motor [A].
PF = 1.0.
L
= Length of submersible drop cable [m].
ρ
= Specific resistance: 0.02 [Ωmm
U
= Nominal voltage [V].
ΔU = Voltage drop [%] = 4 %.
The 4 % voltage drop is according to IEC 3-64, HD-
384 Series.
The calculation gives the following maximum cable
lengths at a supply voltage of 240 V:
Motor
I
N
(P2)
[kW]
[A]
0.7
5.2
1.15
8.4
1.55
11.0
1.85
12
12
2
/m].
Maximum cable length [m]
2
2.1 mm
/
2
1.5 mm
14 AWG
80
112
50
69
37
52
35
49
Cable size
2
3.3 mm
/
2
2.5 mm
12 AWG
133
176
83
109
62
82
58
76
2
2
4 mm
6 mm
213
320
132
198
99
149
92
139