9.
With flame proven at the end of PTFI, the main flame trial for ignition (MTFI) period begins.
Terminal 7 is energized. The BLV512 displays:
Terminal 5 is de-energized 10 seconds later and Terminal 6 is de-energized after another 5 seconds.
10.
The firing rate motor is sent to the automatic modulation position (10-11 circuit made) and is
under the command of the proportional controller. The BLV512 displays:
Normal Shutdown
1.
When the operating control circuit (L1-3) opens, the main fuel valve is de-energized. The firing
rate motor is driven to the low purge position (10-12 circuit made).
2.
Following a 15 second post purge, the burner/blower motor is de-energized.
3.
The burner is now off and the BLV512 displays:
38
PTFI
20
FLAME SIGNAL
MTFI
35
FLAME SIGNAL
AUTO
40
FLAME SIGNAL
POST PURGE
0:05
CYCLE COMPLETE
STANDBY
L1-3 OPEN