Figure 13. Burnerlogix Tyb110Dc/Yb230Dc With 85Uvf4-1Qdwr Scanner; Table 16: Phoenix Scanner Cable Color Code - Fireye BurnerLogiX YB110 Manual

Microprocessor-based integrated burner management control
Hide thumbs Also See for BurnerLogiX YB110:
Table of Contents

Advertisement

3.
BMS = Burner Management System (by others). Do not use Red as 24 volt ground.
4.
External 2.0 Amp fuses recommended.
5.
A safety ground screw is provided on the scanner end plate. An external ground wire must be
installed if line voltage is applied to the relay contacts.
Table 16:
PHOENIX SCANNER CABLE COLOR CODE
NEW 59-546 CABLE COLOR CODE
(Connector Pin No.)
(2) Black
(6) Blue
(8) Yellow
(5) Orange
(7) Brown
(3) Tan
(4) Violet
(1) Red
Shield Drain Wire
FIGURE 13.
BURNERLOGIX TYB110DC/YB230DC WITH 85UVF4-1QDWR SCANNER
FUNCTION
24 vdc Input (+)
24 vdc Input (-)
Flame Relay Contact (n.o.)
Flame Relay Contact (n.o.)
Fault Relay Contact (n.c.)
Fault Relay Contact (n.c.)
4-20 ma Analog Output (+)
4-20 ma Analog Output (-)
Earth Ground
®
OLD 59-497 CAPTIVE-CABLE COLOR CODE
For reference only
Black / Red
White / Blue
White / Red
White / Black
Red
Pink
Violet
Grey / Red
Shield Drain Wire