Siemens SIMATIC NET Operating Instructions Manual page 14

Network components/profibus, optical link module
Hide thumbs Also See for SIMATIC NET:
Table of Contents

Advertisement

Description of the device
2.5 LED display
LED color
LED status
Red
Flashing
Red/green
Flashing
14
Meaning
Transmission rate not yet detected because:
There is no transmitting bus node
There is no connection to a partner module that is trans-
mitting frames
Send and receive FO cable swapped over
Transmission rate does not correspond to the PROFIBUS
standard
There is only one single active bus node connected that
is only transmitting tokens to itself. After activating a sec-
ond bus node, the display must change (token frames
alone are not enough to set the transmission rate).
The connected RS-485 segment is only terminated at one
end
No connection to the master
FO cable interrupted
Problem on the RS-485 interface (bus short-circuit)
Transmission rate detected but:
The slot time of the network could not yet be detected
(network parameter HSA set too low, there is no transmit-
ting bus node)
One optical channel is set to the "redundant optical ring"
mode but the second one is not (this mode must always
be set on both optical channels)
The slot time of the network is set too low
Operating Instructions, 01/2020, C79000-G8976-C270-06
Signaling contact
Does not signal
Does not signal