70304G WITH mA-OUTPUT

The controller 70304G is also available with a mA-output. This output is also configurable. The output
signal and the temperature range are adjustable.

17.1 ADJUSTING SIGNAL TYPE AND TEMPERATURE RANGE

To adjust the signal type and temperature range:
PGM-key, USEr,
up to Conf, PGM-key,
PGM-key, Fnct,
SiGn, PGM-key, SiGn blinking, with
0 = 0-10V
1 = 2-10V
2 = 0-20mA
3 = 4-20mA (factory setting)
Takeover of the adjusted value takes place after 2sec.
up to 0Pnt (zero point of the temperature range): PGM-key, 0Pnt blinking, with
point (0,0 = factory setting).
up to End (end point of the temperature range): PGM-key, End blinking, with
point (200,0 = factory setting).
18

DECOMMISSIONING

N O T E !
No particular measures are necessary for brief decommissioning of the temperature controller.
18
The place of installation of the temperature controller must be protected
from frost also in the time in which the unit is deactivated.
Temperature controller 70304G | 1.00.02
up to OutP, PGM-key,
or
choose signal type:
up to OutA, PGM-key, Out6,
or
adjust zero
or
adjust end