Setting outdoor unit option switch and key function
❋ During "Discharge mode of DC link voltage", voltage of INV1 and INV2 will be displayed alternately.
❋ Even when the outdoor unit power is off, it is dangerous when you come in contact with inverter PCB and fan PCB since
they are charged with high DC voltage.
❋ When replacing/repairing the PCB, cut-off the power and wait until the DC voltage is discharged before replacing/
repairing them. (Wait for more than 15 minutes to allow it to discharge naturally.)
❋ When there were error, 'Dicharge mode of DC link voltage' may not have been effective. Especialy if error E464 and E364
have been occured, power element might be damaged by fire and therefore, do not use the 'Discharge mode of DC link
voltage' .
K3 (Number of
press)
1 time
K1
K2
K3
K4
(A Type)
K4 (Number of
press)
1 time
2 times
3 times
4 times
5 times
6 times
Discharge temperature (Compressor 1)
7 times
Discharge temperature (Compressor 2)
8 times
IPM temperature (Compressor 1)
9 times
IPM temperature (Compressor 2)
10 times
11 times
12 times
13 times
14 times
15 times
TOP temperature (Compressor 1)
16 times
TOP temperature (Compressor 2)
17 times
18 times
19 times
20 times
84
KEY operation
Intialize (Reset) setting
KEY operation
Outdoor unit model
Order frequency (Compressor 1)
Order frequency (Compressor 2)
High pressure (MPa)
Low pressure (MPa)
CT sensor value (Compressor 1)
CT sensor value (Compressor 2)
Suction temperature
COND OUT temperautre
Temperature of liquid pipe
Outdoor temperature
EVI inlet temperature
EVI outlet temperature
Main EEV1 step
Display on segment
Same as initial state
(B Type)
Display on segment
SEG 1
1
AM160FXV✴✴✴✴
2
3
4
5
6
7
8
9
A
B
C
D
E
F
G
H
I
J
K
2000 steps
SEG2, 3, 4
Off, 1, 6
120 Hz
1, 2, 0
120 Hz
1, 2, 0
1.52 MPa
1, 5, 2
0.43 MPa
0, 4, 3
87 °C
0, 8, 7
87 °C
0, 8, 7
87 °C
0, 8, 7
87 °C
0, 8, 7
2 A
0, 2, 0
2 A
0, 2, 0
-42 °C
-, 4, 2
-42 °C
-, 4, 2
-42 °C
-, 4, 2
-42 °C
-, 4, 2
-42 °C
-, 4, 2
-42 °C
-, 4, 2
-42 °C
-, 4, 2
-42 °C
-, 4, 2
2, 0, 0