Samsung AM JXVAF Series Installation Manual page 79

Table of Contents

Advertisement

Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Emergency
operation for
Individual
compressor
malfunction
Cooling capacity
Main
correction
Capcity correction
Main
for heating
Current restriction
Individual
rate
Oil collection
Main
interval
Temperature to
trigger defrost
Main
operation
0
0
0
1
0
0
0
2
0
0
0
1
0
2
0
1
0
3
0
4
0
5
0
6
0
0
0
1
0
2
0
3
0
2
0
4
0
5
0
6
0
7
0
8
0
0
0
1
0
2
0
3
0
4
0
5
0
3
0
6
0
7
0
8
0
9
1
0
1
1
0
0
0
4
0
1
0
0
0
5
0
1
Function of the option
Disabled (Factory default)
Set compressor 1 as
malfunction state
Set compressor 2 as
malfunction state
7-9 (Factory default in case
of A type PBA)
5-7 (Factory default in case
of B type PBA)
9-11
10-12
11-13
12-14
13-15
3.0 (Factory default)
2.5
2.6
2.7
2.8
2.9
3.1
3.2
3.3
100% (Factory default)
95 %
90 %
85 %
80 %
75 %
70 %
65 %
60 %
55 %
50 %
No restriction
Factory default
Shorten the interval by 1/2
Factory default
Apply setting when the
product is being installed
in humid area such as near
river or lake
Remarks
E560 will occur when all
the compressors are set as
malfunction state.
Targeted evaporation
temperature [°C].
(When low temperature value is
set, discharged air temperature of
the indoor unit will decrease)
Targeted high pressure [MPa].
(When low pressure value is set,
discharged air temperature of the
indoor unit will decrease)
When restriction option is set,
cooling and heating performance
may decrease.
79