Optional item
Input unit SEG1 SEG2 SEG3 SEG4
Energy control
Operaton
Main
(B type PBA)
Rotation defrost
Main
(HR only)
Expand
operational
temperature
Main
range for cooling
operation (HR
only)
Channel address
Main
Snow
accumulation
Main
prevention control
Unused option
Main
Unused option
Main
Speed operation
Main
Max. capacity
restriction
Main
(B type PBA)
Gasleak
Pumpdown
Main
(B type PBA)
Unused option
Main
LA KIT option (B
Main
type PBA)
Emergency
oeration for
indoor unit
Main
communication
error (B type PBA)
Base Heater (B
Main
type PBA)
0
0
0
1
1
0
0
2
0
0
1
1
0
1
0
0
1
2
0
1
A
U
1
3
0 ~ 15
0
0
1
4
0
1
1
5
0
0
1
6
0
0
0
0
1
7
0
1
0
0
1
8
0
1
0
0
1
9
0
1
2
0
0
0
0
0
2
1
0
1
0
0
0
1
2
2
0
2
0
0
2
3
0
1
Function of the option
Basic (Factory default)
Energy saving
Power
Disabled (Factory default)
Enabled
Disabled (Factory default)
Enabled
Automatic setting (Factory
default)
Manual setting for channel
0~15
Enabled (Factory default)
Disabled
Unused option
Unused option
Disabled (Factory default)
Enabled
Enabled (Factory default)
Disabled
Disabled (Factory default)
Enabled
Unused option
Disabled (Factory default)
Enabled
Disabled (Factory default)
Indoor high humidity
condition (operation for up
to 12 hours)
Indoor low humidity
condition (operation for up
to 24 hours)
Disabled (Factory default)
Enabled
Remarks
Energy control option of
designated operation sequence
❋ Operating in energy saving
mode, capacity might
decrease compared to normal
operation mode
When enabled, continuous
heating operation is possible
but heating performance will
decrease during rotation defrost
operation
When enabled, continuous
cooling operation is possible even
in low temperature condition up
to -15°C, but noise of the MCU will
increase
Address for classifying the
product from upper level
controller (DMS, S-NET 3, etc.)
During snow accmulation , the fan
may spin even when the unit is
not in operation
Unused option by this model
Unused option by this model
Enabling this setting will
command the air conditioner to
cool/heat faster at initial start-up
However, this function will not
work when High-head condition
setting or Long-piping condition
setting is enabled.
Restrict excessive capacity
increase when operating indoor
units with small capacity
If the gas leak occurred it should
be entered in the pumpdown
operation.
Unused option by this model
Set when LA Kit is installed.
When set, emergency operation
is possible even if an indoor
communication error occurs.
Set when Base Heater is installed.
81