® POWER SYSTEMS, INC. Owner’s Manual Liquid-cooled, Prepackaged Standby Generators Model No.: 004920-0 This manual should remain with the unit. ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT INSTALLATION!!
Thank you for purchasing this model of the standby the operator read this Owner's Manual and thor- generator set product line by Generac Power Systems. oughly understand all instructions before using this Every effort was expended to make sure that the equipment.
Important Safety Instructions Generac Liquid-cooled 20 kW Generator SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe operation be copied and posted in potential hazard areas. Safety should be stressed to all operators, potential operators, and service and repair technicians for this equipment. SAVE THESE INSTRUCTIONS –...
Page 5
Important Safety Instructions Generac Liquid-cooled 20 kW Generator • Inspect the generator regularly, and promptly repair • Generators installed with an automatic transfer or replace all worn, damaged or defective parts using switch will crank and start automatically when NOR- only factory-approved parts.
Section 1 - General Information Generac Liquid-cooled 20 kW Generator GENERATOR When requesting information or ordering parts for this equipment, make sure to include all information This equipment is a liquid-cooled, engine-driven gen- from the RATING DECAL. erator set. The generator is designed to supply elec- trical power that operates critical electrical loads TRANSFER SWITCH ENCLOSURE during utility power failure.
Page 7
Section 1 - General Information Generac Liquid-cooled 20 kW Generator Before connecting wiring cable to terminals, remove 1.7.1 2-POLE MECHANISMS any surface oxides from the cable ends with a wire These switches (Figure 1.1) are used with a single- brush. If ALUMINUM conductors are used, apply phase electrical system, when the single-phase NEU- joint compound to conductors.
Section 1 — General Information Generac Liquid-cooled 20 kW Generator AUTOMATIC SYSTEM OPERATION 1.11 GENERATOR FUEL SYSTEM When this generator, along with its transfer switch, has The unit has been factory tested and adjusted using been installed and interconnected, a circuit board in a natural gas liquid fuel system.
Page 9
CR37 LED2 LED1 CUT R83 CR41 2002 GENERAC POWER SYSTEMS, ASSY #076009A FOR 50HZ 1.12.5 PCB OPERATION LED’S • LED 1 is RED. This LED will be on when UTILITY sensing is NOT available to the circuit board. This LED will function only when the AUTO/OFF/ MANUAL switch is set in the AUTO position.
Section 1 - General Information Generac Liquid-cooled 20 kW Generator 1.12.6 OVERCRANK SHUTDOWN 1.15.2 ENGINE SPECIFICATIONS After 90 seconds of crank-rest cycles, this function Make................Mitsubishi ends cranking if the engine fails to start in that time Displacement ..........92 inches (1.5 liters) period.
Section 1 — General Information Generac Liquid-cooled 20 kW Generator 4. Remove pipe plug from Port 2. 5. Install brass hose fitting into Port 2. 6. Install pipe plug into Port 1. Any attempt to crank or start the engine 7.
Section 2 — Installation Generac Liquid-cooled 20 kW Generator GENERATOR MOUNTING AND EMERGENCY CIRCUIT ISOLATION SUPPORT METHOD Retain the generator compartment to a concrete slab This method prevents overloading the generator by with 1/4-inch masonry type anchor bolts. Be sure the keeping electrical loads below the wattage/amperage bolts are long enough to retain the compartment.
Section 2 — Installation Generac Liquid-cooled 20 kW Generator Proper grounding helps protect personnel against Battery electrolyte fluid is an extremely caustic electrical shock in the event of a ground fault condi- sulfuric acid solution that can cause severe tion in the generator or in connected electrical burns.
Section 2 — Installation Generac Liquid-cooled 20 kW Generator When using maintenance-free batteries, it is not nec- 2.10.3 FUEL SYSTEM essary to check the specific gravity or electrolyte level. Make sure the fuel supply system to the generator (a) Have these procedures performed at the intervals delivers the correct fuel at the correct pressure and specified in Section 4, “Maintenance.”...
Section 3 — Operation Generac Liquid-cooled 20 kW Generator CONTROL CONSOLE 3.1.5 METER READING SELECTOR SWITCH COMPONENTS This switch allows selection of either line-to-line or line-to-neutral voltage and amperage readings on the The components of a liquid-cooled generator control console AC voltmeter and ammeter. console (Figure 3.1) are as follows: 3.1.6 HOURMETER Figure 3.1 - Liquid-Cooled Generator Panel...
Section 3 — Operation Generac Liquid-cooled 20 kW Generator NOTE: WEEKLY EXERCISE CYCLE This fuse will not remove the + battery input The generator will start and exercise once every seven power from the PCB when it opens. This means days.
Section 3 — Operation Generac Liquid-cooled 20 kW Generator ENGINE HEATER This Generac standby generator comes equipped To avoid damaging the transfer switch, per- with a block heater (Figure 3.3), similar to the block form functional tests in the exact order given. heaters used in automotive applications.
Section 3 — Operation Generac Liquid-cooled 20 kW Generator ◆ 3.10 MANUAL OPERATION 3.10.1 CLOSE TO NORMAL SOURCE SIDE Before proceeding, verify the position of the switch by DANGER observing window “A” in Figure 3.5 on page 18. If win- dow “A”...
Page 20
Section 3 — Operation Generac Liquid-cooled 20 kW Generator Figure 3.5 — Actuating Transfer Switch 4. On the generator panel, set the AUTO/OFF/ MANUAL switch to MANUAL position. The gener- ator should crank and start. Failure to do so may result in damage to cer- 5.
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator 3.12 GENERATOR TESTS UNDER LOAD MAINTENANCE PERFORMED BY 1. Set the generator's main circuit breaker to its AUTHORIZED SERVICE FACILITIES OFF or OPEN position. 2. Manually actuate the transfer switch main con- A.
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator 4.4.2 BATTERY FLUID Check battery electrolyte fluid at least once weekly. The exhaust system parts from this product get Fluid should cover separators in all battery cells. If extremely hot and remains hot after shutdown. fluid level is low, add distilled water to cover tops of High grass, weeds, brush, leaves, etc.
Page 23
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator 4.5.7 INSPECT EXHAUST SYSTEM Figure 4.2 - Oil Filter Inspect the exhaust system at least once every three months. Check all exhaust system pipes, mufflers, clamps, etc. for condition, tightness, leaks, security, damage.
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator 4.5.12 SPARK PLUGS Finally, have the insulation resistance of stator and rotor windings checked. If insulation resistances are Reset the spark plug gap or replace the spark plugs excessively low, the generator may require drying. as necessary.
Page 25
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator Battery electrolyte fluid is an extremely caustic 4.6.4 BATTERY REPLACEMENT sulfuric acid solution that can cause severe When replacing batteries, use the same number and burns. Do not permit fluid to contact eyes, skin, the type of battery that follows: clothing, painted surfaces, etc.
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator SCHEDULED MAINTENANCE Following is a recommended maintenance schedule for Generac small standby and residential generator sets. The established intervals in the schedule are the maximum recommended when the unit is used in an average service application.
Page 27
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator Maintenance Level 1 Level 2 Level 3 Level 4 Tasks Recom- Task Required Task Required Task Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done (Date- 3 months/ (Date-...
Page 28
Section 4 — Maintenance Generac Liquid-cooled 20 kW Generator Maintenance Level 1 Level 2 Level 3 Level 4 Tasks Recom- Task Required Task Required Task Task mended Comp. to be done Comp. to be done Comp. Required Comp. to be done (Date- 3 months/ (Date-...
Section 6 - Electrical Data Generac Liquid-cooled 20 kW Generator Wiring Diagram — Control Panel — Drawing No. 0E0344A FOR PRE-PACK TRANSFER SWITCH CONNECTIONS 11 12 USE BLUE WIRE FOR 240V, 1 PHASE USE YELLOW WIRE FOR 208V, 3 PHASE INSULATE UNUSED WIRE END 225A BLUE...
Page 31
Section 6 - Electrical Data Generac Liquid-cooled 20 kW Generator Wiring Diagram — Control Panel — Drawing No. 0E0344A ALTERNATE TR1 (BLUE) (RED) (BLACK) (BLACK) OUTPUT CONNECTION 120/240V. 1- PHASE E1 TO E2 240. E1 TO 00 120V. E2 TO 00 BRUSH HOLDER MOUNTING SCREW 4 RED...
Page 32
Section 6 - Electrical Data Generac Liquid-cooled 20 kW Generator Wiring Diagram — 1.5L — Drawing No. 0E5463-A DC-VR CONTROL PANEL CONNECTION DC-A 12-V. 1 1 2 BLACK BATTERY LEGEND TO 120V/15A BLACK CC - CONTROL CONTACTOR UTILITY FED WHITE DIS - DISTRIBUTOR CIRCUIT DCA - DC ALTERNATOR...
Page 33
Section 6 - Electrical Data Generac Liquid-cooled 20 kW Generator Electrical Schematic — 1.5L — Drawing No. 0E5466 Generac ® Power Systems, Inc. 31...
Page 50
Section 7 - Exploded Views and Parts Generac Liquid-cooled 20 kW Generator Governor Assembly — Drawing No. 0E1331-B ITEM (13) NEOPRENE COATING WIRE HARNESS SECURE WIRE HARNESS WITH TIE WRAP AS SHOWN. "A" TO "A" INTAKE MANIFOLD (REF.) CARBURETOR ARM (REF.) ITEM PART NO.
Page 51
Section 7 - Exploded Views and Parts Generac Liquid-cooled 20 kW Generator Battery — Drawing No. 0E0770A STARTER SOLENOID TO ENGINE BLOCK ITEM PART NO. QTY. DESCRIPTION 077483 BATT 12VDC 75-AH 26 038804D CABLE BATT RED #4 X 20.00 038805B CABLE BATT BLK #4 X 23.00 0742600133 ASSY,WIRE#16 RED 1.5...
Page 52
Section 7 - Exploded Views and Parts Generac Liquid-cooled 20 kW Generator Muffler — Drawing No. 0E4296-B ITEM PART NO. QTY. DESCRIPTION 020689 MUFFLER W/RAIN SHLD 060366 MUFFLR STRAP 6IN DIA 059933 ELBOW 90D 2NPT 080761 NIPPLE TOE 2NPT X 4.5 BLK IRON 059939 RAIN CAP 2.37 I.D.
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the Generac Warranty may provide a longer warranty period.
Page 55
Section 9 – Warranty Generac Liquid-cooled 20 kW Generator EMISSION CONTROL SYSTEM WARRANTY Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines: (a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con- tinue for 24 consecutive months thereafter.
Page 56
Generac Service Facility, and only applies to permanently wired and mounted units. • A Generac Power Systems, Inc. Transfer Switch is highly recommended to be used in conjunction with the genset. If a Non - Generac Power Systems, Inc. Transfer Switch is substituted for use and directly causes damage to the genset, no warranty coverage shall apply.