2.7 Minimum safety clearances
1 m
min.
0.60 m
min. (*)
HEATED AREA
(*) For minimum 20° inclination
Do not locate in heated areas, inflammable materials ( max = 70°C), gas piping and
electrical wiring.
Where safety clearances cannot be respected, heat-protection must be provided
above the heaters.
2.8 Inclination of heaters
Inclination "I" = at least 10° (check SBM survey)
BA BLOCK
IN LOW POSITION
For double speed heaters
Always light the top burner first
HEATED
AREA
0.20 m
100%
OPERATION
XFR 16
: 1.20 m
XFR 20
: 1.30 m
XFR 24
: 1.40 m
XFR 32
: 1.60 m
XFR 48
: 2.00 m
XFR 64
: 2.30 m
50%
OPERATION
1 m min.
I = 10 to 35°
16