2.10 Electrical connections

See diagram of a standard installation. (§2.2 and 2.3, page 7)
Electrical connections must comply with I.E.E. Regulations.
No tension, even momentary between NEUTRAL conductor
and GROUNDED CONDUCTOR
In case of installation without Neutral (or neutral of bad
quality), use an isolation transformer in order to create
an artificial neutral. For that, connect one outlet socket to the
ground.
All heaters must be GROUNDED.
Control : XFR heaters are controlled by VisioLon Ind-T programmable controller.
Refer to the technical instructions.
Electric cables and the electrical junction box must not be positioned in the heated area
around a heater.(see §2.7 page 16)
Types of connection cable
Control unit to RP3 (and RP3 to RP3)
Control unit to RP32 (and RP32 to RP32)
RP3 or RP32 to heater
Control unit to sensor
Number of RP3 and
Fixing RP3 and
Always place the plastic cover back on the top of the screw head.
The RP3 or RP32 box must be located no more than 3 meters away from the ignition
block (BA block) of the heater, as the prewired plug is 3 m long.
It must not be located in the heated area around the heater (see §2.7 page 16)
LINK
units :
1 RP3 per type XFR 16, XFR 20, XFR 24 and XFR 32.
RP32
1 RP32 per type XFR 20-2, XFR 24-2 and XFR 32-2
XFR 48-2 and XFR 64-2.
units :
see instructions supplied in box.
RP32
60 mm
TYPE OF CABLE
2
3-core 0.75mm
85°C temperature rated PVC
sheathed cable to BS6500 Table 9.
2
4-core 0.75mm
85°C temperature rated PVC
sheathed cable to BS6500 Table 9.
Use the BA connector supplied with the
heater
green/yellow wire:
blue wire:
brown wire:
Use the coaxial cable supplied by SBM.
(in 20m, 60m or 300m roles)
60 mm
230V AC
230V AC
L + N + Pe
To control unit
EARTH
NEUTRAL
LIVE
19