CaptiveAire EWC Installation, Operation And Maintenance Manual page 19

Extinguishing system
Table of Contents

Advertisement

Nozzles must be installed from 0" to 6" into the protected area of the duct. When more than 1 ADP nozzle
is required (modular protection), each nozzle must be located at the center of its protected module area.
Additional nozzles are not required for changes in direction*. Duct obstructions and common ductwork
must be protected in accordance with this manual, NFPA 17A and NFPA 96.
ADP nozzle location and aim for duct protection are shown in Figure 21 and Figure 22.
*When a change in direction occurs less than 6" from the duct entrance, the nozzle must be aimed as
shown in Figure 21 and Figure 22.
Figure 21 - Single Nozzle Placement (0-50" Perimeter Duct)
Square Duct
12.5"
(318mm)
Max
Vertical Duct
C L
1. ADP Nozzle
2. Horizontal Duct Centerline (CL)
3. Aim Point
4. Vertical Duct Centerline (CL)
5. Duct Entrance
• Duct perimeter up to and including 50" (1270mm).
• To determine the perimeter: 2(A) + 2(B) = 50" (1270mm).
Round Duct
16" Nom.
(404mm)
1
0-6"
(0-152mm)
(51-102mm)
5
19
Rectangular Duct
A
Vertical/Horizontal Duct
C L
C L
2-4"
A. Rectangular Duct Width
B. Rectangular Duct Length
B
2
3
4
1