5.7

Securing the burner to the boiler

Prepare an adequate system of hoisting by hooking onto the
rings 3)(Fig. 13).
 Slip the thermal protection (standard equipment) onto the
blast tube 4)(Fig. 13).
 Place entire burner on the boiler hole arranged previously,
see (Fig. 12), and fasten with the screws given as standard
equipment.
The burner-boiler seal must be airtight.
WARNING
5.8

Accessibility to the interior of the combustion head

In order to reach inside the combustion head (Fig. 14) proceed as
follows:
 disconnect the electrical wiring related to oil pump/servomo-
tor, air servomotor and gas pressure switch;
 disconnect the leverages related to air damper and head
movement;
 unscrew the 4 x fixing screws 1);
 Release the cable of the electrode 2);
 Disconnect the oil pipes by unscrewing the two connectors
3).
While unscrewing, some fuel may leak out.
WARNING
 Release the ignition pilot retainer;
 Remove the screw/gas pressure test point 6) of the combus-
tion head;
 unscrew the under part of the elbow until it comes free of its
slot;
 Extract the internal part 5) of the combustion head.
5.9

Position of electrodes

Place the electrode on the ignition pilot observing
the dimensions specified in Fig. 15.
WARNING
20027766
Installation
8
7
D10556
1
2
2
D10557
0
18.5
- 2
Diffuser
18
GB
3
3
4
5
3
7
6
71.5
± 1
Electrode
1
2
5
4
1
Fig. 13
8
Fig. 14
D9218
Fig. 15