7.3
Opening the burner
Disconnect the electrical supply from the burner
by means of the main system switch.
DANGER
Turn off the fuel interception tap.
DANGER
Wait for the components in contact with heat
sources to cool down completely.
D10558
7.4
Closing the burner
Refit following the steps described but in reverse order; refit all
burner components as they were originally assembled.
After carrying out maintenance, cleaning or
checking operations, reassemble the hood and all
the safety and protection devices of the burner.
Maintenance
Remove the tie rod 1) (Fig. 45) of the head movement lever,
loosening nut 2).
Disconnect the gas servomotor test point 3).
Disconnect the gas pressure switch socket 4).
Remove screws 5).
At this point it is possible to open the burner at the hinge.
5
5 3 4
5
1
2
5
37
GB
Fig. 45
20027766