Local status and diagnostic indicators

UL
Figure 5
Local status and diagnostic indicators
Designation
Color
UL
Green U
BF
Red
SF
Red
RDY
Green/
yellow/
red
105731_en_01
BF
RDY
SF
D
E
Meaning
State
ON
Logic
OFF
Communica-
ON
tion error (Bus-
Fail)
Flashing
Flashing
OFF
System failure
ON
(PROFINET)
OFF
Flashing
Ready
Green
ON
Flashing
green/
yellow
Flashing
green,
yellow on
Yellow
ON
Yellow
flashing
Flashing
yellow/
red
Red
flashing
OFF
www.phoenixpowersupply.co.uk
Description
Communications power supply present.
Communications power supply not present.
No link status available on any port
SF LED not flashing: Link status available, no communication con-
nection to the PROFINET controller
SF flashing: Hardware watchdog triggered
A PROFINET controller has established an active communication
connection to the PROFINET device.
PROFINET diagnostics available
PROFINET diagnostics not available
Flashes only together with the BF LED; watchdog triggered
Device is ready for operation.
Communications power undervoltage or surge voltage
Overtemperature
Device is in standby mode.
Firmware/bus coupler is booting
Firmware update is being performed.
Firmware update has failed.
Faulty firmware
Device is not ready to operate.