Diagnostic Indicators For Profinet; Diagnostic Alarms; Startup - Phoenix Contact AXL F BK PN Manual

Axioline f bus coupler for profinet
Table of Contents

Advertisement

9
Diagnostic indicators for
PROFINET
States during operation
LED
Meaning
SF OFF/
PROFINET controller was able to establish
BF OFF
communication without errors.
States in the event of an error
LED
Meaning
SF OFF/
PROFINET de-
BF flash-
vice is waiting
ing
for communica-
tion with the
PROFINET con-
troller.
The logic com-
munication con-
nection has
been inter-
rupted. The
PROFINET con-
troller can no
longer be ac-
cessed.
The PROFINET
device is not as-
signed a PROFI-
NET device
name.
SF OFF/
The physical
BF ON
communication
path has been
interrupted. The
PROFINET con-
troller can no
longer be ac-
cessed.
SF ON/
Diagnostic data
BF OFF
is available.
SF flash-
Hardware
ing/
watchdog has
BF flash-
been triggered.
ing
105731_en_01
Measure/remedy in the
event of an error
No error
Check the connection be-
tween the PROFINET con-
troller and the PROFINET
device. Make sure that the
PROFINET device name of
the PROFINET device is
identical with the configura-
tion.
Assign the PROFINET de-
vice name using the relevant
tool.
Restore the physical con-
nection between the
PROFINET controller and
the PROFINET device.
Read the diagnostic mes-
sage using the relevant tool.
Execute a reset. Replace
the device when the error
occurs again.
www.phoenixpowersupply.co.uk
States during firmware update
LED
Meaning
RDY
BootP requests are sent and the firmware con-
flashing
tainer is loaded via tftp.
RDY ON /
Firmware is saved.
M ON
The firmware update can take several min-
utes.
The bus coupler is restarted automatically af-
ter a successful update.
10

Diagnostic alarms

PROFINET enables the PROFINET device to store diagnos-
tic information together with the error location and error type.
In the default upon delivery the alarms are enabled, how-
ever, they can be disabled with parameters on startup.
An incoming alarm informs the PROFINET controller that di-
agnostic information has been stored.
When the diagnostic information has been removed, an out-
going alarm is transmitted to the controller.
If at least one piece of diagnostic information is stored, the
SF LED is on. If no diagnostic information is present, the SF
LED is off.
11

Startup

Default upon delivery/default settings
By default upon delivery, the following functions and fea-
tures are available:
PROFINET name:
IP parameters:
Module designation:
Vendor ID:
Device ID:
Firmware started
Once you have supplied the bus coupler with power or
pressed the reset button, the firmware is started. After com-
pletion of the firmware boot process the BF LED is either on
or flashing.
AXL F BK PN
No name assigned
0.0.0.0
AXL F BK PN
00B0
hex
1000
hex
PHOENIX CONTACT
10

Advertisement

Table of Contents
loading

This manual is also suitable for:

2701815

Table of Contents