Parameterization

PC Worx
Parameterization of the PROFINET device in PC Worx re-
quires at least PC Worx Version 6.30. This is part of the
AUTOMATIONWORX Software Suite 1.80 and 1.81.
An online data sheet of the device with important technical
data and a configuration file are integrated into PC Worx. If
several versions of the configuration file are available, make
sure that you are working with the file version that corre-
sponds to the firmware/hardware version used.
Other tools
The PROFINET device is parameterized using the configu-
ration tool of the PROFINET controller. Please integrate the
corresponding GSDML file of the bus coupler into the rele-
vant software tool (STEP 7/HW Config, ...).
Make sure you always use the latest version
of the FDCML/GSDML file and the latest doc-
umentation for the bus coupler. The latest files
and documentation can be found on the Inter-
net at phoenixcontact.net/products.
14

Device replacement

Devices can be replaced without having to reconfigure them
within the PROFINET network. The station name and ad-
dress are assigned by the control system to the newly added
PROFINET bus coupler using the neighborhood detection
function.
15

Phoenix Redundancy Layer (PRL)

The Phoenix Redundancy Layer (PRL) makes it possible to
design a redundant system with two PROFINET controllers.
One controller is configured as the primary I/O controller and
the other as the backup I/O controller. Depending on which
PROFINET controller provides valid values, the bus coupler
operated at field level adopts these values or uses failsafe
values.
PRL (or shared device) and MRP can be used
simultaneously if the PROFINET update time
is 8 ms and the PROFINET watchdog time is
> 200 ms.
105731_en_01
16
Dynamic configuration on the local
bus
You can use the "Dynamic configuration" function with this
bus coupler.
Dynamic configuration is the specification and configuration
of a maximum configuration. Any subgroup of this maximum
configuration can be operated.
17

Substitute value behavior

When PROFINET communication breaks down or an error
occurs in the local bus, all outputs of the Axioline F station
are set to the parameterized substitute values. The local bus
continues to run with these values.
18

WBM - Web-based management

The device has a web server, which generates the required
pages for web-based management and, depending on the
requirements of the user, sends them to a standard web
browser. Web-based management can be used to access
static information (e.g., technical data, MAC address) or dy-
namic information (e.g., IP address, status information).
Calling web-based management
The device web server can be addressed using the IP ad-
dress if configured accordingly. The homepage (web page)
of the device is accessed by entering the URL
"http://ip-address".
Example: http://172.16.113.38
19

Firmware update

In order to update the firmware of the bus coupler, the device
must be provided with a firmware container via a TFTP
server. You can use any TFTP server, e.g., Factory Man-
ager.
Please refer to the "Diagnostic indicators for PROFINET"
section for the LED states during the firmware update.
www.phoenixpowersupply.co.uk
The TFTP FIRMWARE UPDATE application
note describes how to update the firmware us-
ing the Factory Manager.
This document can be found on the Internet at
phoenixcontact.net/products.
PHOENIX CONTACT
AXL F BK PN
12