Binary Inputs (BI), continued..
NPA
98
99
100
101
102
103
3
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
130
131
132
133
134
135
136
24
Unit
Description
13
Braking
12
Braking Max
11
Brake Check Ok
10
Output Frequency Low
9
Output Frequency High
8
Output Current Low
7
Output Current High
6
Feedback Low
5
Feedback High
4
Catch Up
3
Slow Down
2
Start CW/CCW
1
AMA Running
0
Ramping
9
Ramp
15
Reverse
14
Setup MSB
13
Setup LSB
12
Relay02
11
Relay01
10
Res., always 0 (data valid)
8
Jog
7
Reset
6
Start
5
Freeze Output
4
Q-stop
3
Coast
2
DC Brake
1
Preset ref. MSB
0
Preset ref. LSB
0
Terminal 33
1
Terminal 32
2
Terminal 29
3
Terminal 27
4
Terminal 19
5
Terminal 18
6
GPIO Term X30/2
7
GPIO Term X30/3
8
GPIO Terminal X30/4
Selection
AF-600 FP Par. Number
0=FALSE, 1=TRUE
0=Remote ref., 1=Local ref.
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
Par. DR-94 Ext. Status Word
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=RAMP 1, 1=RAMP 2
0=No function, 1=reverse
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=Relay04 off, 1=Relay04 on
0=Relay01 off, 1=Relay01 on
0=FALSE
0=No Function, 1=Jog
Par. DR-00 Control Word
0=No Function, 1=Reset
0=start, 1=stop
0=Freeze output, 1=Ramping
0=Q-stop, 1=Ramping
0=Coasting, 1=no Coast
0=DC Brake, 1=Ramp stop
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
0=FALSE, 1=TRUE
AF-600 FP Metasys
Par. DR-60 Digital Input