GE AF-600 FP Metasys Operating Instructions Manual page 17

Table of Contents

Advertisement

2.2.1 Start-up of the Frequency Converter
Use the frequency converter keypad mounted either on the drive or remote. Use the Extended Menu key to access the O-## group parameters (Options / Comms).
The settings shown below are typical. Some settings may be changed to meet the application requirements. The settings below will serve as a good starting
reference. Refer to the operating instruction manual for instructions on changing parameters and programming the drive.
2
Examples of typical settings. Program the following:
par. O-30 Protocol
par. O-31 Address
par. O-32 Drive Port Baud Rate
par. O-50 Coasting Select
par. O-52 DC Brake Select
par. O-53 Start Select
par. O-54 Reversing Select
par. O-55 Set-up Select
par. O-56 Preset Reference Select
par. O-94 Bus Feedback 1
par. O-95 Bus Feedback 2
NB!
Send an F command to begin communications between the master and the drive!
Example 1:
Device address
Char1 command
Checksum
Message code:
>XXFYY <CR>
Example 2:
Network start, BO override command:
Device address
Char1 command
Char1 subcommand
Char2 region
Char2 object number (NPA)
Char2 override value
Checksum
Message code:
>XX72040401YY <CR>
16
Parameter:
F command
Setting:
[3] Metasys N2
1 (Default)
[2] 9600 Baud (fixed at 9600 for N2 protocol)
[3] Logic OR
[3] Logic OR
[3] Logic OR
[0] Digital input
[3] Logic OR
[3] Logic OR
0
0
Setting:
XX
F
YY
Issue a run command through the master, to the device:
Setting:
XX
7
2
04
04 (Start)
01 (Active)
YY
Issue a frequency reference through the master, to the device:
AF-600 FP Metasys