LED
H204
H501
H500
4.4.1
4.4.1.1
Button
Function
S202
Reset main microprocessor on
main board
4.4.1.2
Button
Function
S203
Switch resets current state of
Aux and NAC LEDs
4.4.1.3
Button
Function
S300
Disconnects releasing service
from ability to activate
Siemens Industry, Inc.
Building Technologies Division
Color
Condition
Yellow
Blinking
Yellow
OFF
ON
Green
OFF
ON

Switches

S202 Main Board RESET
Position
Not pressed
Pressed
S203 Reset for NAC Status LEDs
Position
Not pressed
Pressed
S300 Releasing Manual Disconnect
Position
EN
DIS
Model PAD-5-CLSA
Meaning
Indicates main microprocessor is processing data
P2 - Normal condition
P2 - Trouble Condition
P2 – Pattern not Locatable
P2 – Pattern Locate
Meaning
Normal
Resets only the main microprocessor on
the periphery board.
Meaning
Previous state of NACs and Aux circuits
Steady: In Trouble
Blinking: Was in Trouble (Currently Normal)
Clears previous state and reports current
state of NACs and Aux circuits
Meaning
-Releasing is ready in standby
Releasing cannot activate when in this
position