TR-Electronic SSI-BOX Operating Manual

TR-Electronic SSI-BOX Operating Manual

Converter for ssi into profibus-dp according to pno-profile class 2
Table of Contents

Advertisement

Quick Links

Converter for SSI into PROFIBUS-DP
according to PNO-Profile Class 2
SSI-BOX Art.-No.: 489-00004 and variations
Variations
Edition-/Rev.-Date:
25.04.2012
Document-/Rev.-No.: TR - E - BA - GB - 0013 - 03
Soft edition:
File name:
TR-E-BA-GB-0013-03.DOC
Author:
MÜJ
TR - Electronic GmbH
Eglishalde 6
D-78647 Trossingen
Telephone
++49 (0)7425 / 228-0
Telefax
++49 (0)7425 / 228-33
SSI-BOX
489-00003 (with Incremental-Interface, TTL-Level)
489-XXXXX (with Incremental-Interface, UP-Level 5...24 V)
Please keep for further use !
will be defined!
Enclosed Disk
Art.-No.: 490-00406

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SSI-BOX and is the answer not in the manual?

Questions and answers

Summary of Contents for TR-Electronic SSI-BOX

  • Page 1 SSI-BOX Converter for SSI into PROFIBUS-DP according to PNO-Profile Class 2 SSI-BOX Art.-No.: 489-00004 and variations 489-00003 (with Incremental-Interface, TTL-Level) Variations 489-XXXXX (with Incremental-Interface, UP-Level 5...24 V) will be defined! Please keep for further use ! Edition-/Rev.-Date: 25.04.2012 Document-/Rev.-No.: TR - E - BA - GB - 0013 - 03...
  • Page 2 Fax: (0049) 07425/228-33  Copyright 1997 TR-Electronic Guarantee In our ongoing efforts to improve our products, TR-Electronic reserve the right to alter the information contained in this document without prior notice. Printing This manual was produced on a personal computer using MS-Word for Windows. The text was printed in Arial type.
  • Page 3 ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) Revision History Note: The cover of this document shows the current revision status and the corresponding date. Since each individual page has its own revision status and date in the footer, there may be different revision statuses within the document.
  • Page 4: Table Of Contents

    2.2.2 Requirements for start-up on SIMATIC-S7 ................ 14 2.2.3 Requirements for start-up on other PROFIBUS master devices ........14 3 Characteristics of the SSI-BOX / Commissioning ................... 15 3.1 SSI-BOX PNO identification number ....................15 3.2 Type file / device master file ......................15 3.3 Start-up on PROFIBUS ........................
  • Page 5 3.7 Preset adjustment ..........................31 3.8 SSI interface ............................31 3.9 Optional Incremental-Interface ......................32 4 Characteristics of the SSI-BOX (connection of linear encoders) ............33 4.1 SSI-BOX PNO identification number ....................33 4.2 Type file / device master file ......................33 4.3 Start-up on PROFIBUS ........................
  • Page 6: Safety

    1 Safety 1.1 General Potential for Danger The SSI-BOX cannot function as a stand-alone unit, i.e. it is a component part that is intended to be installed in a complete system consisting of several such components working together. This means that the SSI-BOX does not have a direct protection device of its own.
  • Page 7: Installation Information

    Operating Manual SSI-BOX PROFIBUS-DP (PNO) 1.2.1 Installation information Due to the fact that the SSI-BOX is normally used as a component part of a larger system, this information is intended to provide a guideline for safe installation of the device in its environment.
  • Page 8: Wiring The Converter Housing

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 1.2.1.1 Wiring the converter housing Note In addition to the connection terminals, the converter housing contains all the electronics for converting SSI signals that come from the encoder into appropriate Profibus data. To protect the electronics from environmental influences, we chose a housing that complies with type of protection IP 67 according to DIN 40 050.
  • Page 9: Connecting The Cable Screening To The Converter Housing

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 1.2.1.2 Connecting the Cable Screening to the Converter Housing To prevent disturbance signals entering the converter housing, we used cable screw glands with which it is possible to connect the screen on the inside. For this reason, no connection point for the screen is provided inside the converter housing.
  • Page 10: Appropriate Use

    Linear encoders without checksum, 24 data bit, binary, exclusively usable for the nominal configuration "Box+rotary encoder TR Gear" The SSI-BOX can be parameterized via the PROFIBUS according to the PNO profile and is designed to be run on PROFIBUS-DP networks according to DIN 19245 Part 1- 3 up to a maximum of 12 Mbauds.
  • Page 11: Danger Due To Accessories

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) Caution  Always keep to the operating temperature range of -20° to +70° C!  Keep to the sealing of the converter housing (see note on page 10), principal when industrial liquids to run over the housing!
  • Page 12: Authorized Operators

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 1.5 Authorized Operators This device may only be commissioned by qualified personnel. In the context of the safety-specific information in this document, qualified personnel are considered to be persons who are authorized to commission, ground and mark circuits, equipment and systems in accordance with recognized safety standards.
  • Page 13: Transportation / Commissioning

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 2 Transportation / Commissioning 2.1 Transportation / Storage Transportation Information Do not drop the device or subject them to excessive jolting! Use only the original packaging material! Incorrect packaging material can cause damage to the device in transit.
  • Page 14: System Requirements

    (*.200) for COM-ET-200 for Windows (art.no. 490-00406). 2.2.2 Requirements for start-up on SIMATIC-S7 In order to start up the SSI-BOX on a programmable controller of the SIMATIC S7 type, the following minimum requirements must be met:  STEP-7 for Windows Version 2.1 Edition 4 or higher. The Version 2.1 basic...
  • Page 15: Characteristics Of The Ssi-Box / Commissioning

    An encoder exchange only do when the voltage is switched off. 3.1 SSI-BOX PNO identification number The SSI-BOX has the PNO ID number AAAB (hex). This number is reserved and filed with the PNO. 3.2 Type file / device master file The type files used with the SSI-BOX have the filename "TRSS00XX.200"...
  • Page 16: Which Configuration Is To Be Used

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 3.4 Which configuration is to be used? The type file or device master file contains four nominal configurations for the PNO Class 1 and 2, each with 16 and 32-bit resolution and two nominal configurations for TR-specific extensions.
  • Page 17: Which Ssi-Format Do The Configurations Need

    LSB (2 The encoder absolutely must have the programming, which is specified above. The SSI-BOX is reduced in the programming (see use notes of this configuration on page 23). TR - ELECTRONIC GmbH, Global Quality Management, Eglishalde 6, 78647 Trossingen, Tel. ++49 (0)7425-228-0, Fax ++49 (0)7425-228-33 Date: 25.04.2012...
  • Page 18 The encoder absolutely must have the programming, which is specified above. The SSI-BOX is reduced in the programming (see use notes of this configuration on page 23). Starting from software version 011 no restriction (see chapter 4 page 33).
  • Page 19: Configuration And Parameterization

    PROFIBUS master (a programming via "EPROG"-program is not possible). For this purpose, the type file of the SSI-BOX must be copied into the relevant directory for type files. In the case of some programs, such as COM PROFIBUS or STEP7 Manager, the internal equipment list (hardware catalogue) has to be updated within the software.
  • Page 20: Box+Rotary Encoder Class-1/16, Identifier 0Xd0 (208 Dec.)

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 3.6.1.1 Box+rotary encoder class-1/16, identifier 0xD0 (208 dec.) The SSI-BOX uses one input word only, which is consistently transferred via the bus. Input word IW x Data byte 1 Data byte 0 Input byte x+0...
  • Page 21: Box+Rotary Encoder Class-2/16, Identifier 0Xf0 (240 Dec.) / 1Ax (Simatic-Manager)

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 3.6.1.3 Box+rotary encoder class-2/16, identifier 0xF0 (240 dec.) / 1AX (Simatic-Manager) The SSI-BOX uses one input word and one output word which are consistently transferred via the bus. Input word IW x Data byte 1...
  • Page 22: Box+Rotary Encoder Tr Gear, Identifier 0Xf1 (241 Dec.) / 2Ax (Simatic-Manager)

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 3.6.1.5 Box+rotary encoder TR Gear, identifier 0xF1 (241 dec.) / 2AX (Simatic-Manager) The SSI-BOX uses two input words and two output words which are consistently transferred via the bus. Double input word ID x...
  • Page 23 ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 3.6.1.5.1 Use notes Rotary encoder SSI without checksum (CRC) Specified SSI-BOX configuration  Code sequence arbitrary  Encoder CRC checksum monitoring switched off  Total measuring range (units) hi  Total measuring range (units) lo ...
  • Page 24 ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) Linear encoder, TR configuration "Box+rotary encoder TR Gear" (only up to software versions 010) SSI without checksum (CRC) Specified SSI-BOX configuration  Code sequence arbitrary  Encoder CRC checksum monitoring switched off ...
  • Page 25: Parameterization

    - decreasing to the end of the rod 3.6.2.2 Class 2 functionality Defines the SSI-BOX's range of functions. "Class 2 deactivated" means that the SSI-BOX only performs Class 1 functions, does not scale the position value and is not adjustable. Selection (Box+rotary encoder class-2/16, class-2/32) Default ...
  • Page 26: Measuring Units Per Revolution

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 3.6.2.5 Measuring units per revolution Defines the number of increments displayed by the encoder for each revolution of the encoder shaft. Input (Box+rotary encoder class-2/16, class-2/32)  Lower limit 1 increment / revolution ...
  • Page 27: Revolutions Denominator

    - 1 Warning To execute a preset the preset-inputs of the SSI-BOX have to be used. Possible available preset-inputs of the encoder may not be used to set the position. TR - ELECTRONIC GmbH, Global Quality Management, Eglishalde 6, 78647 Trossingen, Tel. ++49 (0)7425-228-0, Fax ++49 (0)7425-228-33 Date: 25.04.2012...
  • Page 28: Preset 2 Value [Units] Hi And Preset 2 Value [Units] Lo

    - 1 Warning To execute a preset the preset-inputs of the SSI-BOX have to be used. Possible available preset-inputs of the encoder may not be used to set the position. TR - ELECTRONIC GmbH, Global Quality Management, Eglishalde 6, 78647 Trossingen, Tel. ++49 (0)7425-228-0, Fax ++49 (0)7425-228-33 Date: 25.04.2012...
  • Page 29 ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) Notes for the input of parameters with data format 32 bits The Profibus standard DIN 19245 provides the data format "UNSIGNED32" for the definition of 32 bits of parameter data in the device master file. This data format isn't supported by all configuration programs for profibus master.
  • Page 30: Notes For The Scaling Function

    3.6.3 Notes for the scaling function 3.6.3.1 Nominal configurations "Box+rotary encoder class-1 / class-2" The SSI-BOX does not support a broken number of revolutions. The position value is decoded in binary form and balanced against a zero offset and the code sequence.
  • Page 31: Preset Adjustment

    The preset adjustment value transferred in data bytes 0 - 3 is accepted as the position value with the leading edge of bit 32 (=bit 7 of data byte 3). The SSI-BOX then continues counting from this position. A readjustment is not possible until the control bit has been reset again.
  • Page 32: Optional Incremental-Interface

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 3.9 Optional Incremental-Interface The incremental information of the encoder (K1, /K1, K2, /K2) is supplied at connector X10, passed through the driver stage and can be tapped off at connector X11. These outputs are potential-free! Variations (see also pin assignment in the appendix): Option 1 (Art.-No.: 489-00004, main device)
  • Page 33: Characteristics Of The Ssi-Box (Connection Of Linear Encoders)

    An encoder exchange only do when the voltage is switched off. 4.1 SSI-BOX PNO identification number The SSI-BOX has the PNO ID number AAAB (hex). This number is reserved and filed with the PNO. 4.2 Type file / device master file The type files used with the SSI-BOX have the filename "TRSS00XX.200"...
  • Page 34: Configuration And Parameterization

    PROFIBUS master. For this purpose, the type file of the SSI-BOX must be copied into the relevant directory for type files. In the case of some programs, such as COM PROFIBUS or STEP7 Manager, the internal equipment list (hardware catalogue) has to be updated within the software.
  • Page 35 ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) Class 1 16-bit resolution, identifier D0 (HEX): The SSI-BOX uses one input word only, which is consistently transferred via the bus. Input word IW x Class 1 32-bit resolution, identifier D1 (HEX): The SSI-BOX uses two input words only, which are consistently transferred via the bus.
  • Page 36 ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) Class 2 32-bit resolution, identifier F1 (HEX): The SSI-BOX uses two input words and two output words which are consistently transferred via the bus. Double input word ID x Double output word for preset adjustment OD x...
  • Page 37: Use Notes

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 4.4.2 Use notes Linear encoder, TR configuration "Box+linear encoder" (starting from software version 011) SSI with checksum (CRC) Specified SSI-BOX configuration  Code sequence arbitrary  Encoder CRC checksum monitoring switched on ...
  • Page 38: Parameterization

    (movement of the position sensor toward the end of the rod) 4.4.3.2 Class 2 functionality: Defines the SSI-BOX's range of functions. "Class 2 deactivated" means that the SSI-BOX only performs Class 1 functions, does not scale the position value and is not adjustable. Selection ...
  • Page 39: Measuring Units Per Meter Hi And Measuring Units Per Meter Lo

     Upper limit 65536 4.4.3.6 Preset 1 value [units] hi and preset 1 value [units] lo This parameter define the position value to which the SSI-BOX is adjusted with the leading edge of the 1st preset input. Inputs for HI word ...
  • Page 40: Preset 2 Value [Units] Hi And Preset 2 Value [Units] Lo

    Operating Manual SSI-BOX PROFIBUS-DP (PNO) 4.4.3.7 Preset 2 value [units] hi and preset 2 value [units] lo This parameter define the position value to which the SSI-BOX is adjusted with the leading edge of the 2nd preset input. Inputs for HI word ...
  • Page 41: Preset Adjustment

    The preset adjustment value transferred in data bytes 0 - 3 is accepted as the position value with the leading edge of bit 32 (=bit 7 of data byte 3). The SSI-BOX then continues counting from this position. A readjustment is not possible until the control bit has been reset again.
  • Page 42: Trouble-Shooting And Diagnostic Facilities

    ELECTRONIC GmbH Operating Manual SSI-BOX PROFIBUS-DP (PNO) 5 Trouble-shooting and diagnostic facilities 5.1 Visual indicators LED „STAT“ (green) LED „BF“ (red) The SSI-BOX is equipped with two LEDs. One red LED (BF) for indicating errors and one green LED (STAT) for indicating status information.
  • Page 43: How To Use The Profibus Diagnostics

    Operating Manual SSI-BOX PROFIBUS-DP (PNO) 5.2 How to use the PROFIBUS diagnostics The SSI-BOX supplies the diagnostic information for Class 1 and Class 2 of the profile for encoders issued by the PROFIBUS User Organisation (PNO). A copy of this profile is obtainable exclusively via the PNO office.
  • Page 44: Appendix

    - with 15 bit CRC, 28 data bits, binary Linear encoders: ....... - without CRC, 24 data bits, binary Length of cable encoder<->SSI-BOX . by length of cable adjustment max. 1000m possible (with checksum evaluation) SSI data interface: Structure: ........... Data: 2-wire acc. to EIA RS422 Pulses: Opto-coupler input Cable type: ........
  • Page 45: General Instructions For Cabling

    Operating Manual SSI-BOX PROFIBUS-DP (PNO) 6.2 General instructions for cabling If the SSI-BOX is the last station on the Profibus line, the DIP switches for the Profibus terminator must be switched on (connection of terminating resistor). Otherwise, these switches must be switched off.

Table of Contents